

Add to Cart
Application
The cables are mainly used in energy networks with sudden load change residental or industrial areas. Can be laid outdoors, under grounds and in areas where sudden mechanical stress are expected
Construction
Technical data:
Specification
Nominal section area |
Approx. overall diameter |
Approx. weight of cable |
Maximum DC resistance of the conductor |
||
mm2 |
mm |
kg/km |
Ω/km |
||
|
|
Cu |
Al |
20℃ Cu |
20℃ Al |
1×1.5 RE |
9 |
160.2 |
– |
12.1 |
– |
1×2.5 RE |
9.4 |
178.5 |
135.7 |
7.41 |
12.1 |
1×4 RE |
10.3 |
202.6 |
178.4 |
4.61 |
7.41 |
1×6 RE |
10.8 |
232.4 |
196.2 |
3.08 |
4.61 |
1×10 CC |
11.8 |
292.1 |
231.7 |
1.83 |
3.08 |
1×16 CC |
12.8 |
368.1 |
271.5 |
1.15 |
1.91 |
1×25 CC |
14.4 |
481.1 |
326.4 |
0.727 |
1.2 |
1×35 CC |
15.4 |
595.4 |
378.8 |
0.524 |
0.868 |
1×50 CC |
17.2 |
782.2 |
472.9 |
0.387 |
0.641 |
1×70 CC |
18.8 |
1002.1 |
569 |
0.268 |
0.443 |
1×95 CC |
20.7 |
1285 |
697.2 |
0.193 |
0.32 |
1×120 CC |
22.2 |
1548 |
805.6 |
0.153 |
0.253 |
1×150 CC |
24.1 |
1879.8 |
951.7 |
0.124 |
0.206 |
1×185 CC |
26.2 |
2264.9 |
1120.3 |
0.0991 |
0.164 |
1×240 CC |
28.9 |
2853.8 |
1369 |
0.0754 |
0.125 |
1×300 CC |
31.6 |
3493.6 |
1637.5 |
0.0601 |
0.1 |
1×400 CC |
35.2 |
4530.9 |
2056.1 |
0.047 |
0.0778 |
1×500 CC |
40.2 |
5966.8 |
2873.3 |
0.0366 |
0.0605 |
1×630 CC |
43.9 |
7302.1 |
3404.3 |
0.0283 |
0.0469 |