Forced Draught Air Cooled Heat Exchanger with API 661, Petroleum Industry

Selection of Induced Draught or Forced Draught

The air-cooled heat exchanger shall be either a forced-draught exchanger or an induced-draught exchanger and shall include the components shown in Figure 1 and any auxiliaries such as ladders, walkways and platforms. Forced-draught fans should be used, except that induced-draught fans should be considered for the following situations:


  • a) If temperature control of the process is critical and sudden downpour of rain (i.e. excessive cooling) can cause operating problems;
  • b) To minimize the risk of hot-air recirculation;
  • c) On sites where air-side fouling is a significant problem, however forced draft can be used if screens are specified;
  • d) To improve thermal performance in the event of a fan failure (due to the stack effect);
  • e) In hot climates, where the fan plenum chamber shields the bundle from the sun;
  • f ) For services that have a temperature approach of 11 °C (20 °F) or less


A) Forced DraughtB) Induced Draught
1Tube Bundle6Fan
2Header7Fan Ring
3Nozzle8Fan Deck
4Supporting Column9Drive Assembly
5Plenum10Fan Guard

[Figure 1]



Construction of Tube Bundle

Tube bundles shall be rigid, self-contained, and designed for handling as a complete assembly.

Typical Construction of Tube Bundles
1Tubesheet11Tube support cross-member
2Removable cover plate12Tube keeper
3Removable bonnet13Vent
4Top and bottom plates14Drain
5Tube15Instrument connection
6Pass partition 
7Gasket 
8Nozzle 
9Side frame 
10Tube spacer 


[ A) Removable cover-plate header ]

[ B) Removable bonnet header ]



Tubes and Finning

Maximum Fin Selection Temperature for Fin Bonding Types:

Fin Bonding TypeMaximum Process Temperature °C (°F)
Embedded fins400 (750)
Externally bonded
(hot-dip galvanized steel fins)
360 (680)
Extruded fins300 (570)
Footed fins (single L) &
overlap footed fins (double L)
130 (270)
Knurled footed fin,
either single L or double L
200 (390)
Externally Bonded
(welded or brazed fins)
> 400 (750)
(maximum should be negotiated)