Technical Data For YB Pre-installed Substation | ||||||
HV | Ltem | Unit | Date | |||
Rated Frequecy | Hz | 50 | ||||
Rated Voltage | kV | 6 10 35 | ||||
Max Working Voltage | kV | 6.9 11.5 40.5 | ||||
Industrial Requency Voltage-resisting Time / | kV | 32/36 42/48 95/118 | ||||
isolationBallisticVoltage-resisting | ||||||
Thunderand Lighting BallisticVoltage-resistingTime /isolation
SectionalPort | kV | 60/70 75/85 185/215 | ||||
Rated Curent | A | 400 630 | ||||
Rated Brief-period Curent-resisting | kA | 12.5(2s) 16(2s) 20(2s) | ||||
Rated Crest Value Curent-resisting | kA | 32.5 40 50 | ||||
LV | Rated Voltage | V | 380 220 | |||
Rated Current Of Major Retur Circuit | A | 100-3200 | ||||
Rated short-circuit Curent-resisting | kA | 15 30 50 | ||||
Rated Crest Value Current-resisting | kA | 30 63 110 | ||||
Branch Circuit | A | 10-800 | ||||
Quantity Of Branch | line | 1月12日 | ||||
Compensation Circuit | kVAR | 0-360 | ||||
Transtorming | Rated Capacity | kVA | 50-2000 | |||
Short-circuit lmpendance | % | 4 6 | ||||
Scope Of Branch Connection | +2x2.5% ±5% | |||||
Vector Group | Yyn0 Dyn11 |