UMP-400-48 UMP-400-24 Rectifier Module

Brand Name:MEAN WELL
Certification:CE
Model Number:ump-400-24 /UMP-400-48
Minimum Order Quantity:1 piece
Delivery Time:8-10 weeks
Payment Terms:L/C, T/T
Contact Now

Add to Cart

Verified Supplier
Location: Beijing Beijing China
Address: No 803,Unit 3 ,DaDou Road, Huihao Building .Fangshan District,Beijing,China
Supplier`s last login times: within 36 hours
Product Details Company Profile
Product Details


Mean Well UMP Series UMP-400 Series UMP-400-24 UMP-400-48 Rectifier Module


Features :

Fan-less, 1U design

Modular design, with DC-DC module cards (NID35/65/100 series models)

Can be used as a single rail PSU

wide operating temperature ranges from -30 ~ +70 ° C

Meet OVC III requirements

Meet 2x MOPP isolation requirements, ideal for BF rated medical equipment


Technical


MODELUMP-400-24UMP-400-48

SINGLE OUTPUT

(Standard model)

DC VOLTAGE24V48V
RATED CURRENT16.7A8.3A
RATED OUTPUT POWER400W max.
VOLTAGE ADJ. RANGE22.8 ~ 25.2V45.6 ~ 50.4V
RIPPLE & NOISE (max.) Note.2240mVp-p360mVp-p
VOLTAGE TOLERANCE Note.3±1.0%±1.0%
LINE REGULATION±0.5%±0.5%
LOAD REGULATION±1.0%±1.0%
SETUP, RISE TIME1000ms, 50ms/230Vac ; 2000ms, 50ms/115Vac
HOLD UP TIME (Typ.)12ms@230Vac ; 12ms@115Vac

MULTIPLE OUTPUT

(Optional Model)

DC VOLTAGECH1 output 24V or 48V + NID DC modules for CH2,3,4
TOTAL OUTPUT POWERCH2,3,4 output power can be flexible depending on NID selection. Combined power on all channels must not exceed 400W

INPUT

VOLTAGE RANGE Note.490 ~ 264VAC 127 ~370VDC
FREQUENCY RANGE47 ~ 63Hz
POWER FACTORPF>0.95/230VAC PF>0.98/115VAC at full load
EFFICIENCY(Typ.) Note.588.5%, full case load with each type of module at nominal voltage
AC CURRENT2.5A/230VAC 4.7A/115VAC
INRUSH CURRENT40A/230VAC 25A/115VAC
LEAKAGE CURRENTEarth leakage current <300uA / 264VAC, Touch current <100uA/264VAC

PROTECTION

OVERLOAD105 ~ 135% rated output power
Protection type CH1: constant current limiting protection ( If a long short circuit continues, the OTP action will be triggered ), CH2,CH3,CH4: Hiccup mode protection
OVER VOLTAGE26.4 ~ 31.2V52.8 ~ 62.4V
Protection type: shut down o/p voltage, re-power on to recover
OVER TEMPERATUREShut down o/p voltage, re-power on to recover

ENVIRONMENT

WORKING TEMP.-30 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY20 ~ 90% RH non-condensing
STORAGE TEMP.-40 ~ +85℃
TEMP. COEFFICIENT±0.03%/℃ (0 ~ 50℃)
VIBRATION10~500Hz, 2G 10min./1 cycle, 60 min. each along X, Y, Z axes
OPERATING ALTITUDE Note.65000 meters /OVCⅡ
OVER VOLTAGE GATEGORYⅢ; According to IEC62368-1; altitude up to 2000 meters

SAFETY & EMC

(Note 7)

SAFETY STANDARDSEAC TP TC 004; UL62368-1, Dekra seal BS EN/EN62368-1 approved; Design refer to ANSI/AAMI ES60601-1, TUV BS EN/EN60601-1, IEC 60601-1 (3rd edition)
ISOLATION LEVELPrimary-Secondary: 2x MOPP, Primary-Earth: 1x MOPP
WITHSTAND VOLTAGEI/P-O/P: 4KVAC I/P-FG: 2KVAC O/P-FG: 1.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC / 25℃/ 70% RH

EMC EMISSION

ParameterStandardTest Level / Note
ConductedBS EN/EN55032 (CISPR32) / Design refer to BS EN/EN55011 (CISPR11)Class B
RadiatedBS EN/EN55032 (CISPR32) / Design refer to BS EN/EN55011 (CISPR11)Class B
Harmonic CurrentBS EN/EN61000-3-2Class A
Voltage FlickerBS EN/EN61000-3-3-----

EMC IMMUNITY

BS EN/EN55035; Design refer to BS EN/EN60601-1-2
ParameterStandardTest Level / Note
ESDBS EN/EN61000-4-2Level 4, 8KV air; Level 4, 4KV contact
RF fieldBS EN/EN61000-4-3Level 3, 3V/m
EFT/ BurstBS EN/EN61000-4-4Level 3, 1KV
SurgeBS EN/EN61000-4-5Level 4, 2KV/Line-FG; 1KV/Line-Line
ConductedBS EN/EN61000-4-6Level 2, 3V
Magnetic FieldBS EN/EN61000-4-8Level 1, 1A/m
Voltage Dips and InterruptionsBS EN/EN61000-4-11

100% dip 1 periods, 30% dip 25 periods,

100% interruptions 250 periods


OTHERS

MTBF1428.4K hrs min. Telcordia SR-332 (Bellcore) ; 187.3K hrs min. MIL-HDBK-217F (25℃)
DIMENSION250*89*37mm (L*W*H)
PACKING0.88Kg; 14pcs/13Kg/0.89CUFT

NOTE

1. All parameters NOT specifically mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.

3. Tolerance: includes set up tolerance, line regulation and load regulation.

4. De-rating may be needed under low input voltages. Please check the derating curve for more details.

5. The efficiency changes by installing different output modules.

6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m (6500ft).

7. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by

mounting the unit on a 450mm*450mm metal plate with 3mm of thickness. The final equipment must be re-confirmed that it still meets

EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”

(as available on http://www.meanwell.com)

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx











Solutions
We provide a complete solutions including site survey, propose professional plan according to customer’s request ,technical support, and maintenance service for Telecommunication Companies in and out of China. We have a competent team and a network of trusted Partners around the world.

FAQ :
1. How do you control the quality?
A:All products before the shipment are simulated usage scenarios, load and full load and current sharing test to ensure the quality of the product.

2. What is your minimum order quantity?
A:There is no minimum order quantity, and one can also be done. The only difference is the price and schedule.

3. Can you introduce your company?
A:I am very honored. I will send you the company’s introduction document later to give you a more comprehensive and direct introduction to our company’s information.

4. What are the advantages of your company?
A:Adequate inventory, and supply guarantee for the subsequent renewal of supply, flexible provided according to different to different needs of customers, providing different solutions.

5. Can i send samples?Report it to me along with the price?
A:You can send samples, the samples are subject to large pride, and the freight needs to be borne by you.

6. How do your company deal with the problem on quality?
A:Our company has been doing this industry for almost 10 years. It has already had a certain reputation. We will carefully analyze it. If it is indeed our quality problem, you can rest assured that it will do things according to the contract agreement and will never let you have any after the worries, our service team will be happy to serve you.

7 What about the quality ?
A:100% original with new package. we will test each item before posted to make sure each item with good quality.
8 How many months for guarantee ?
A: 1 year quality guarantee
9 How to deal with any inferior -quality goods ?
A: Goods can be post by with our charge of post fee for any bad quality products within guarantee time.







China UMP-400-48 UMP-400-24 Rectifier Module supplier

UMP-400-48 UMP-400-24 Rectifier Module

Inquiry Cart 0