WATER-C200 200seats 1200KW water cooling Container box marine
certification
Version | Supercomputer water cooling container WATER-C-200 |
Size | 6058*2438*2896mm |
Miner seats | 200 units |
Container certification | China marine certification |
Safety certificate | North America:NFPA 79:2021,UL 508A:2018 R8.21, |
CSA C22.2 No. 14-18,ANSI/ISO 12100:2012 | |
EU/certificate:EN ISO 12100,EN 60204-1 | |
working power (kW) | 1250KW |
PUE(Power usage efficiency) | 1.022(excluding cooling tower)/1.036 (including cooling tower) |
Input voltage and frequency | 415V±5% 60Hz(North America) |
400V±5% 50Hz(EU, Middle East) | |
Shipping weight(T) | 6T |
Working weight (T) | 12T |
Main switch of power distribution cabinet(A) | 1200(North America) |
1250(EU, Middle East) | |
Rated current(A) | 952 |
Standard power(kW) | 1200 |
Maximum power(kW) | 1050 |
Rated current of each miner(A) | 10 |
incoming cable | The incoming cable can withstand high voltage above 600V, and the requirements for each phase are as follows: |
L1 single core cable600kcMil(300mm²)x4 | |
L2 single core cable600kcMil(300mm²)x4 | |
L3 single core cable600kcMil(300mm²)x4 | |
N single core cable 600kcMil(300mm²)x4 | |
PE single core cable 500kcMil(240mm²)x2 | |
Connection interface (cooling tower) | DN125(GB/T 9119-2010 PN16 DN125) |
Connection interface (plate heat exchange interface) | DN100(GB/T 9119-2010 PN16 DN100) |
(m³/h) | >85 |
Use environment requirements
1 The cooling tower is required to be placed on a flat ground,
level (±1 degree).
2 The ground is required to be hardened and stable, capable of
bearing a load of at least 14 tons.
3 Unloading the WATER-C and cooling tower requires a crane over 10
tons.
4 The delivery of the WATER-C does not include additional items
such as stairs, transformers, cables, trays and cable distribution
boxes. Our team can provide design advice if needed.
5 The customer needs to confirm the opening direction of the box,
and needs to face the air inlet. The door on the left is the
default current design.
6 Allow at least 2 meters of air intake space around the cooling
tower.
7 Altitude: ≤3000m. If the altitude is higher than 1000 meters, the
transformer and switch should be derated. For every 100 meters of
altitude, the total power of ANTSPACE must be reduced by 1%.
8 Operating temperature: -25°C to 40°C.
Operating humidity: 10%RH to 90%RH.
When the initial coolant temperature is lower than 20°C, the
internal circulation should be turned on to heat the coolant to
above 20°C before starting the miner.
9 When the ambient temperature is lower than 5℃, the cooling tower
can be switched to the cold-drying mode.
10 Select pure water or suitable antifreeze as coolant according to
local climate conditions.
WARRANTY
1. 365 days warranty from the date of shipment. When shipping a replacement device during the warranty period, we will be responsible for the shipping cost.
2. The warranty applies only to the original purchaser directly
from us. Once the miner is resold, the warranty coverage becomes
the reseller's responsibility.
3. If the user does not use the product in accordance with the
instructions, specifications and conditions provided, or changes
the functional settings of the device without our prior consent, we
will not be liable for any loss caused thereby.
4. The specifications of the equipment are based on the order
batch, and the specific parameters of the model are changed without
prior notice.