ST505 Stationary Ultrasonic Energy Meter

Integrate into your management system to provide remote measurement services.


Product Information


ST505 is a high-accuracy ultrasonic energy meter with clamp-on transducers measuring big pipe diameter, which is built-in RTD module. When it is equipped with PT100 temperature sensor, ST505 can be upgraded into energy meter used for measuring individual energy consumption in any liquid heating/cooling systems. The meter is supplied complete with flowmeter and temperature sensor, which can makes the system real-time detect the temperature of supply and return pipe.


The energy meter can be widely applied in various applications, like HVAC, cooling tower, data center, energy audit, and building(shipping mall, office, museum, hospital, school, subway etc.). Energy meter, also called thermal energy meter or heat meter, is used to accurately measure heat consumption in heating and cooling facilities so as to reach energy-saving and cost-saving.


ST505 is a brand-new high-end product that is made of aluminum alloy material and realizes CNC processing method. It adopts the industry-leading full-sealed iron-absorbing side-opening technology without any screw locking, and the tedious steps of screwing are reduced. Such a convenient design truly realizes "one-second opening".


Benefits

  • Measure the actual flow and total consumption of various liquids.
  • No loss of process control, optimization of assets and efficiency, no downtime or expense from calibration.
  • Adaptive signal processing algorithms optimize performance, ensuring accurate measurements even in challenging flow conditions.
  • Clear display interface and LCD display with alarm function, easy to operate and debug
  • Utilize transit-time ultrasonic technology so as to realize bi-directional flow measurement by precisely measuring the time it takes for ultrasonic signals to transmit upstream and downstream.
  • Leverage the data logging capabilities to analyze historical flow patterns to make system optimization.
  • Built-in keypad and simple menu system for fast and easy programming of pipe diameter, pipe material, liquid type, and measurement nuits.

Product Features


Dimension


Transmitter

Transducer

Technical Information


Parameter


Performance Specifications
Velocity Range0.03~±16ft/s (0.01~±5m/s)
Accuracy±1% of measured value
Repeatability0.3% of measured value
Pipe Size1" ~ 48" (25mm ~ 1200mm)
Power Supply24V DC
Keypad16 touch bottons
Display(20×2) ,alphanumeric, backlit LCD.
Function Specifications
OutputAnalog output: 4~20mA, max load 750Ω.
Pulse output: 0~9999Hz, OCT, (min. and max. frequency is adjustable)
Relay output: max 1Hz(1A@125V AC or 2A@30V DC)
CommunicationRS485
Liquidwater, sea water, oil, alcohol...
Pipe MaterialPVC, stainless steel, carbon steel, copper...
Physical Specifications
TransmitterDie-cast aluminum, IP65, CNC machined
TransducerEncapsulated design, protection grade IP68
Double-shielded transducer cable
The standard/maximum length of cable: 30ft/1000ft(9m/305m)
TemperatureTransmitter: -40℉~140℉(-40℃~60℃)
Transducer: 32℉~140℉(0℃~60℃) Standard
PT100 Temp. Sensor: 32℉~257℉(0℃~125℃)
HumidityUp to 99% RH, non-condensing

Installation


V Method

The "V" method is considered as the standard method. It usually gives more accurate reading and is used on pipe diameters ranging from 25mm to 400mm(1'' ~ 16'') approximately. Also, it's convenient to use, but still requires proper installation of the transducer, contact on the pipe at the pipe's centerline and equal spacing on either side of the centerline.


Z Method

The signal transmitted in a "Z" method installation has less attenuation than a signal transmitter with the "V" method. This is because the "Z" method utilizes a directly transmitted(rather than reflected) signal which transverses the liquid only once. The "Z" method is able to measure on pipe diameters ranging from 100mm to 3000mm(4”~120”).


N Method

With the "N" method, the sound waves transverse the fluid twice and bounce three times off the pipe walls. It's suitable for small pipe diameter measurement. The measurement accuracy can be improved by extending the transit distance with the "N" method(uncommonly used).


W Method

As with the "N", the measurement accuracy can also be improved by extending the transit distance with the "W" method. The sound wave transverse the fluid four times and bounces four times off the pipe walls. It's suitable for very small pipe(diameter is less than 50mm/2'').


Wiring


Package & Accessory


Order Information


ST505CodeSpecification
FUitrasonic Flow Meter(Optional)
EUltrasonic BTU/Energy Meter(Standard)
CodeTransducer
CT039Clamp-on transducer:
32℉~140℉ (0℃~60℃)(Standard)
IT215Insertion transducer:
-40F~176F(-40℃~80℃)(Optional)
CodeCable Length
LStandard cable length:33ft(10m)
L+On request other lengths
Code Temperature Sensor
PT100 Temperature:32℉~257℉ (0℃~125℃)
ST505ECT039LComplete ordering information