Home /Electronic Measuring Instruments /

Air Conditioning Chilled Water Flow Measure Meter

Air Conditioning Chilled Water Flow Measure Meter

Brand Name:Flo-Instru
Certification:CE; ISO9001
Model Number:ST501
Minimum Order Quantity:1
Delivery Time:3-5 working days
Payment Terms:T/T
Contact Now

Add to Cart

Verified Supplier
Location: Shenzhen Guangdong China
Address: 2F, Rongxing Building,No.1007 Banxuegang Avenue, Bantian Street, Longgang District, Shenzhen, 518129 Guangdong, China.
Supplier`s last login times: within 40 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

ST501-PT100 Ultrasonic Energy Meter

Clamp-on type ultrasonic energy meters for cooling and heating consumption measurement.


Introduction

ST501-PT100 is an upgraded version of ST501, adding heat energy measurement function, so it can detect flow rate and heat energy consumption of the fluid at the same time.


Main Features

• Precise bi-directional and highly dynamic flow measurement with the non-intrusive clamp-on technology.

• High accuracy at fast and slow flow rates, high temperature and zero point stability.

• Water and liquids, tolerant of liquids with small amounts of air bubbles or suspended solids

• Automatic loading of calibration data and transducer detection for a fast and easy set-up, providing precise and long-term stable results.

• Clear and simple menu selections

• Clamp on transducer and insertion transducer versions

• Transducers available for a wide range of inner pipe diameters (25mm~1200mm) and fluid temperatures (0~80℃)


Applications

Widely used in HVAC, industrial, medical, chemical, environmental and other fields.


Specifications

PERFORMANCE SPECIFICATIONS

Velocity range0 ~ ±16ft/s (0 ~ ±5m/s)
Accuracy

±1.0% of measured value

Energy class: 2

Pipe sizeClamp-on: 1"~48" (25mm~1200mm)
FluidWater, Sea water, Oil, Alcohol...
Pipe materialCarbon steel, stainless steel, PVC...

FUNCTION SPECIFICATIONS

OutputsOCT Pulse output: 0~9999Hz.
Analog output: 4~20mA, max load 750Ω.
Communication interfaceRS485
Power supply24V DC@1Amax
Keypad16(4×4) key with tactile action
Display20×2 lattice alphanumeric, back lit LCD.
TemperatureTransmitter: 32℉~140℉ (0℃~60℃)

Transducer: 32℉~140℉ (0℃~60℃)

Temperature sensor: 32℉~257℉(0℃~125℃)

HumidityUp to 99% RH, non-condensing

PHYSICAL SPECIFICATIONS

TransmitterAluminum alloy, IP65.
TransducerEncapsulated design, IP68.
Transducer cableStandard cable length: 33ft (10m).
WeightTransmitter: approximately 1.0kg;
Transducer: approximately 0.4kg
HT SensorPT100