Add to Cart
Characteristic:
1.7/24/365 video monitoring,each cannon has a 1080P camera.
2.Can tracking moving fire.
3.Automatic tracking,targeting and extinguishing fire.
4.Automatic alarm when there is a fire risk.
5.Temperature and image Sensing technology avoid wrong judgement
Main Components:
1.1080P CCTV camera.
2.UV detector.
3.Infrared thermal imaging flame detector.
4.Laser transmitter.
5.Dual function cannon head,can spray water column and water mist
What's an automatic fire water monitor ?
The Automatic Fire Water Monitor is an automatic firefighting system including control unit and water discharge device.It discharge large volumes of water from a single fixed location, and at high pressure to give it an excellent range of coverage.The Quick Response Fire water Monitor has built-in infrared thermal imaging detector, UV flame detector, closed circuit television camera. Real time dynamic flame location and laser corrector. The Automatic Fire Water Monitor works with the external UV flame detector to eliminate the detection blind area and increase early warning range.
When the Automatic Fire Water Monitor receives the fire early warning signal (UV or IR signal),it will
start to rotate to scanning the fire,it's built-in image IR flame
detector will rotate along with the water monitor and lock the
flame for 3 seconds, then spray water to extinguish the fire.
Otherwise, the water monitor will consider it as a false alarm, and
the Automatic Fire Water Monitor will return to it's initial position.The time spent from fire started to fire targeted is less than 30
seconds.
Specifications:
ZDMS0.6/5S-LZII | ZDMS0.6/10S-LZII | ZDMS0.8/20S-LZII | ZDMS0.9/30S-LZII | ZDMS0.8/40S-LZII | ZDMS0.8/50S-LZII | |
Working Voltage | DC36V | DC36V | DC24V | DC24V | DC24V | DC24V |
Rated Pressure | 0.6MPa | 0.6MPa | 0.8MPa | 0.9MPa | 0.8MPa | 0.8MPa |
Protection Radius | 20m | 28m | 42m | 50m | 52m | 55m |
Rate of flow | 5L/s | 10L/s | 20L/s | 30L/s | 40L/s | 50L/s |
Installation Height | 6~15m | 6~15m | 8~35m | 8~35m | 8~35m | 8~35m |
Jet radius | ≤34m | ≤39m | ≤56m | ≤62m | ≤67m | ≤73m |
Positioning time | ≤30s | ≤30s | ≤60s | ≤60s | ≤60s | ≤60s |
Monitoring radius | 40m | 40m | 60m | 60m | 80m | 80m |
Flange Connection | DN50 | DN50 | DN80 | DN80 | DN100 | DN100 |
Notices:
1.The side of cannon with label”this side to wall” must be faced to
wall when installed.
2.Video line connected from DVR to cannon directly.
3.Signal lines must connect to signal lines of cannon where it is
2m from cannon.
4.Operation panel installed near the exit and 1.5m from ground,and
from where operator can see all cannnons controlled by this
operation panel.
5.Pls take care when handling cannon as there is UV detector at the
bottom of cannon.The UV detetor is fragile.
6.Make sure there is no barrier around the cannon to stop the
cannon 360 degree rotate.
7.The ground lead of DVR,earth wire and Lightning protection wire
of control console need be connected to your ground lead.
Scope of applications:
Our Automatic Fire Water Monitor are wildly used in Industrial,commercial and residential fields.Such as airport, high-speed railway station, bus station, hotel atrium, museum, library, TV studio, gymnasium, science and technology museum, exhibition hall, convention center, theater, cinema, civic activity center, industrial plant, chemical plant, gas station, oil port,helicopter hangar, power plants, logistics centers, hospitals, large shopping malls, commercial complexes, colleges and universities, coal mines, warehouses and other places with large space.