Add to Cart
AB ControlLogix digital I/O module Inputs 32 1756-IB32
Specifications for digital I/O module Inputs 32 1756-IB32
Manufacturer Rockwell Automation
Brand AB
Part Number/Catalog No. 1756-IB32
Series ControlLogix
Inputs 32
Module Type Digital DC Input Module
No. of Inputs Thirty-Two (32) Inputs
Input Voltage 12-24 Volts DC Sink
Operating Voltage Range 10-31.2 Volts DC
Module Keying Electronic
Input Delay Time 2 milliseconds plus selected filter time
Maximum Operating Current 5.5 milliamperes
Minimum Operating Current 2 milliamperes at 10 Volts DC
Maximum Input Current, Off-State 1.5 milliamperes
Input Delay Time, OFF to ON Hardware delay: 380 µs max + filter
time
Input Delay Time, ON to OFF Hardware delay: 420 µs max + filter
time
Backplane Current at 5 Volts 120 milliamperes
Power Dissipation (Max) 6.2 W @ 60 °C (140 °F)
Backplane Current at 24 Volts 2 milliamperes
Backplane Current at 5.1 Volts 100 milliamperes
Thermal Dissipation 21.1 BTU/hr @ 60 °C (140 °F)
UPC 10612598171306
Removeable Terminal Block(s) 1756-TBCH 1756-TBSH
OTHER SUPERIOR PRODUCTS
Yasakawa Motor, Driver SG- | Mitsubishi Motor HC-,HA- |
Westinghouse Modules 1C-,5X- | Emerson VE-,KJ- |
Honeywell TC-,TK- | GE Modules IC - |
ABB Module | AB Module 1756-,1759- Tourch Screen 2711- |
Mitsubishi Drive MR- , Motor HA -,HC | Emerson MoudlesVE- ,KJ - |
Fanuc motor A0-, Drive | Yokogawa transmitter EJA- |
Rosemount Transmitter 3051- | Schneider Module 140- |
Panasonic Motor , Drive MH- | Siemens Module 6ES-, Touch Screen 6AV- |
About digital I/O module Inputs 32 1756-IB32
The AB 1756-IB32 is a ControlLogix digital I/O module. Part of the
ControlLogix system, this input module has 32 inputs available in 2
groups, with 16 points in each group. It is mounted to a
ControlLogix chassis by using the required removable terminal block
housing, or RTB, such as either the AB 1756-TBCH or 1756-TBS6H.
This module, occupies a single slot of the ControlLogix Chassis and
supplied with an open enclosure type. The 1756-IB32 module has an
operating voltage range of 10 to 31.2 Volts DC and a nominal input
voltage of 24 Volts DC. It has a voltage category of 12/24 Volts DC
sink, a current draw of 120 mA at 5.1 Volts and 2 mA at 24 Volts,
and a total backplane power rating of 0.66 W. The maximum power
dissipation is 6.2 W at 60 degrees Celsius, while the thermal
dissipation is 21.1 BTU/hour, also at 60 degrees Celsius.
The AB 1756-IB32 ControlLogix digital I/O module also has a maximum
inrush current rating of 250 mA, which decays to less than 37% in
22 milliseconds without activation. In an off-state, its maximum
current is 2.27 mA and its maximum voltage is 5 Volts. The input
delay time for the off-to-on and on-to-off processes differ. For
the off-to-on process, there is a hardware delay of up to 380
microseconds plus a user-configurable filter time of either 0, 1,
or 2 milliseconds. The on-to-off delay time includes the hardware
delay time of up to 420 microseconds plus the user-configurable
filter time of either 0, 1, 2, 9, or 18 milliseconds.
The AB 1756-IB32 is a High-Density Discrete input module that
belongs to the ControlLogix product family of Programmable
Automation Controllers (PAC). This module features Thirty-Two (32)
input channels, grouped in Two (2) with Sixteen (16) channels each
group.
It may be installed to a local I/O rack or distributed I/O chassis
or in a stand-alone or Distributed Control Systems (DCS) such as
AB’s Plant PAx. One this module is entered through the Hardware
configuration, the module’s parameters are accessible such as the
module’s general properties with important parameters of compatible
keying and slot assignment. This module also has a configurable
Request Packet Interval (RPI), Module Inhibition, Reaction to
communication failure and Scheduled connection over ControlNet.
Each channel of this module has configurable filter settings to
allow fine tuning of the module’s reaction time to signals. This
adjustment is useful in applications where discrete signals are
erratic and exposed to noise. This feature helps prevent false
positive negative readings.
This module is also provided with the capability of self-diagnosis
through the module info where the module’s diagnostic status can be
monitored such as minor and major fault. It can also detect the
status of the ControlLogix backplane where the module is connected.
This module is shipped with a Removable Terminal Block (RTB). This
RTB enables modular replacement of a defective module an provides
ease of wiring the signals. Compatible RTB for this module are
1756-TBCH 1756-TBS6H or a 36-terminal RTB.