Add to Cart
EDJ Fire Pump Set with Discharge Valves and Common Header with jockey pump + electric pump
Fire pump package comprises a combination of electric motor driven pump, diesel engine driven and electric motor driven jockey pumps that supply for fire suppression systems. Fire pump package is required to comply with Local Civil Defense Authority regulations and International Codes of Practice e.g. National Fire Protection Association
100GPM @4BAR | |||||
Pump | Model | Capacity(GPM) | Head(BAR) | Power(KW) | Material |
Electric | XBD4/5-50L(50-200) | 100 | 4 | 5.5 | cast iron |
Diesel engine | XBC4/5-IS | 100 | 4 | 5.5 | cast iron |
Jockey | CDL2-70 | 10 | 5 | 0.75 | SS304 |
100GPM @6BAR | |||||
Pump | Model | Capacity(GPM) | Head(BAR) | Power(KW) | Material |
Electric | XBD6/5-65L(65-250B) | 100 | 6 | 7.5 | cast iron |
Diesel engine | XBC6/5-IS | 100 | 6 | 7.5 | cast iron |
Jockey | CDL2-100 | 10 | 7 | 1.1 | SS304 |
200GPM @6BAR | |||||
Pump | Model | Capacity(GPM) | Head(BAR) | Power(KW) | Material |
Electric | XBD6/10-65L(65-250) | 200 | 6 | 15 | cast iron |
Diesel engine | XBC4/5-IS | 200 | 6 | 22 | cast iron |
Jockey | CDL4-90 | 20 | 7 | 2.2 | SS304 |
500GPM @5BAR | |||||
Pump | Model | Capacity(GPM) | Head(BAR) | Power(KW) | Material |
Electric | XBD5/30-100L(100-200) | 500 | 5 | 22 | cast iron |
Diesel engine | XBC5/30-IS | 500 | 5 | 30 | cast iron |
Jockey | CDL12-60 | 50 | 6 | 4 | SS304 |
500GPM @8BAR | |||||
Pump | Model | Capacity(GPM) | Head(BAR) | Power(KW) | Material |
Electric | XBD8/30-100L(100-250) | 500 | 8 | 37 | cast iron |
Diesel engine | XBC8/30-D | 500 | 8 | 45 | cast iron |
Jockey | CDL12-90 | 50 | 9 | 5.5 | SS304 |
500GPM @10BAR | |||||
Pump | Model | Capacity(GPM) | Head(BAR) | Power(KW) | Material |
Electric | XBD10/30-100L(100-315A) | 500 | 10 | 55 | cast iron |
Diesel engine | XBC10/30-D | 500 | 10 | 55 | cast iron |
Jockey | CDL12-110 | 50 | 11 | 7.5 | SS304 |
750GPM @9BAR | |||||
Pump | Model | Capacity(GPM) | Head(BAR) | Power(KW) | Material |
Electric | XBD9/50-125L(125-250) | 750 | 9 | 55 | cast iron |
Diesel engine | XBC9/50-D | 750 | 9 | 90 | cast iron |
Jockey | CDL16-90 | 70 | 10 | 11 | SS304 |
750GPM @10BAR | |||||
Pump | Model | Capacity(GPM) | Head(BAR) | Power(KW) | Material |
Electric | XBD10/50-150L(150-315A) | 750 | 10 | 90 | cast iron |
Diesel engine | XBC10/50-D | 750 | 10 | 90 | cast iron |
Jockey | CDL16-100 | 70 | 11 | 11 | SS304 |
EDJ series is a packaged fire pump set,generally an automatic fire
water supply system It consists of a main pump (driven by an
electrical motor),stand by pump (driven by diesel engine) and a
jockey pump.This model comes equipped with a separate controller,or
one that is attached to the skid,The package also contains
discharge valves,common header,and accessories.
2. Working Principle
Each pump information(E+D+J) & Controller Information
Diesel engine pump Specs
The diesel engine is fixed on the base with anti-vibration rubber pads and the pump is directly coupled to a diesel engine through flexible coupling, According to the power output of the engine the electrical system,the diesel engine can be Cummins,Deutz,Perkins and Other China brand engine(Shangchai,Yuchai,ec.) and it consists of alternator, started motor, fuel system, lubricating system, exhaust system, etc.
Electric motor pump and Jockey pump
The electric pump is Horizontal Split Case Centrifugal Pump,we also can choose end suction pump and horizontal multistage pump,just as per client's pump specs requirement.
The motor is squirrel cage industrial type and foot mounted suitable for 3 phase, with required hose power rating.
The Jockey pump specs will be choosed as per Diesel engine & electric motor pump specifications.
Controller Information
The common controller is fabricated from mild steel and epoxy
powder coated to red color. The enclosure id IP 54 rated and having
all the required controls complying with the applicable standards
(NFPA).
Manual starting: If set up for the”Manual”position with the black
2# three-way switch on the control panel mode,That you can use
“Manual” start button and “Manual” stop button to control diesel
engine pump start or stop. when the black three-way switch to
the”stop”position,diesel pump can’t work.
Automatic starting: If set up for the”Auto”position with the black
three-way switch on the control panel mode,it will receives an
effective fire alarm signal to control diesel pump start or stop.
Through the pressure controllers on the common outlet pipe to
achieve pressure control.first, use two 1” 1.5 square signal lines
to connect between the pressure controller normally open contacts
and the control cabinet’s terminal No. 111 and 127. then, set a
low-value and high-pressure for pressure controller to achieve
low-voltage to start pump and high-pressure to stop pump. Last,if
the electric main pump is overload,the diesel engine pump will
start.
Double Suction Pump/ clean water pump/cast iron type/horizontal pump