Home /Stencils /

original and new Siemens PLC 6ES7 134-4JB51-0AB0 in stock. discount price

original and new Siemens PLC 6ES7 134-4JB51-0AB0 in stock. discount price

Brand Name:Siemens
Model Number:6ES7 134-4JB51-0AB0
Minimum Order Quantity:1
Payment Terms:T/T, D/A, L/C, L/C, Western Union, MoneyGram
Place of Origin:Germany
Price:130-150usd
Contact Now

Add to Cart

Site Member
Location: Ningbo Zhejiang China
Address: NO.17 Buliding,Zhongshan JINTING,YueLin Street,Fenghua City,Ningbo, Zhejiang,China
Supplier`s last login times: within 1 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

Best Quality Assurance:

1. We only provide theoriginal new items, 100% make sure the best quality!

2. 30-days GUARRANTEE OF QUALITY (After Our Delivery Date).


Payment Methods :

We accept T/T, West Union, PayPal , Escrow payment .


Refound or Replacement:

We accept return back itmes if the goods still remain in their original condition on the warranty time .

6ES7134-4JB51-0AB0
ET200S, EL-MOD., 2/4 AI RTD STANDARD
SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 2/4 AI RTD STANDARD, 15 MM WIDE, 15BIT + SIGN PT100 STD; PT100 KL; NI100 STD; NI100 KL; 150 OHM; 300 OHM; 600 OHM, CYCLE TIME 110 MS/CHANNEL WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
● Rated value (DC)24 V; From power module
● Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.30 mA
from backplane bus 3.3 V DC, max.10 mA
Output voltage
Power supply to the transmitters
● presentYes
● short-circuit proofYes
Power loss
Power loss, typ.0.6 W
Address area
Address space per module
● Address space per module, max.8 byte
Analog inputs
Number of analog inputs4; 2 for 3 or 4-wire connection
permissible input voltage for voltage input (destruction limit), max.9 V
Constant measurement current for resistance-type transmitter, typ.1.67 mA
Cycle time (all channels) max.Number of active channels per module x basic conversion time
Technical unit for temperature measurement adjustableNo
Input ranges
● VoltageNo
● CurrentNo
● ThermocoupleNo
● Resistance thermometerYes
● ResistanceYes
Input ranges (rated values), resistance thermometer
● Ni 100Yes; Standard/climate
● Input resistance (Ni 100)2 000 kΩ
● Pt 100Yes; Standard/climate
● Input resistance (Pt 100)2 000 kΩ
Input ranges (rated values), resistors
● 0 to 150 ohmsYes
● Input resistance (0 to 150 ohms)2 000 kΩ
● 0 to 300 ohmsYes
● Input resistance (0 to 300 ohms)2 000 kΩ
● 0 to 600 ohmsYes
● Input resistance (0 to 600 ohms)2 000 kΩ
Characteristic linearization
● parameterizableYes; for Pt100, Ni100
— for resistance thermometerPt100 (standard, climatic range), Ni100 (standard, climatic range)
Cable length
● shielded, max.200 m
Analog value generation for the inputs
Measurement principleintegrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.16 bit; 150 ohms: 14 bits; 300, 600 ohms: 15 bits, Pt100, Ni100: 16 bits
● Integration time, parameterizableYes
● Integration time (ms)16,7 / 20 ms
● Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
● Conversion time (per channel)66 / 80 ms; additional conversion time for diagnostic wire break test
Smoothing of measured values
● parameterizableYes; In four stages by means of digital filtering
● Step: NoneYes; 1 x cycle time
● Step: lowYes; 4 x cycle time
● Step: MediumYes; 32 x cycle time
● Step: HighYes; 64 x cycle time
Encoder
Connection of signal encoders
● for resistance measurement with two-wire connectionYes
● for resistance measurement with three-wire connectionYes
● for resistance measurement with four-wire connectionYes
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range
● Resistance thermometer, relative to input range, (+/-)0.6 %
Basic error limit (operational limit at 25 °C)
● Resistance thermometer, relative to input range, (+/-)0.4 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min.70 dB
● Common mode interference (USS < 2.5 V) , min.90 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal)No
Interrupts/diagnostics/status information
Diagnostic messages
● Wire-breakYes
● Group errorYes
● Overflow/underflowYes
Diagnostics indication LED
● Group error SF (red)Yes
Parameter
Diagnostics wire breakDisable / enable
Measurement type/rangedeactivated/150 ohms/; 300 ohms/600 ohms/ Pt100 climatic/ Pt100 standard; Ni100 standard / Ni100 climatic, 2, 3 or 4-wire
Group diagnosticsDisable / enable
Overflow/underflowDisable / enable
Potential separation
Potential separation analog inputs
● between the channelsNo
● between the channels and backplane busYes
● Between the channels and load voltage L+Yes
Permissible potential difference
between MANA and M internally (UISO)75 V DC/60 V AC
Isolation
Isolation tested with500 V DC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight40 g