Outdoor Data Cabinet Telecom Power Systems Low Power Consumption GPE4860C


Quick Details:


Place of Origin: Shenzhen, China (Mainland)Input Voltage: AC220V
Brand Name: ESTELOutput Voltage: DC48V
Model Number: GPE4860COutput Power: 3200W
Product Name: Telecom Power SystemInput Frequency 45~65Hz
Certification: ISO9001, CE, 3C, FCC, TLCOutput Current: 60A
Installation Mode: 19” rackPower Factor: 0.98
Application: outdoor UPS cabinet

Components:

2×30A rectifier module,

1×monitoring module,

power distribution


Payment & Shipping Terms:


Minimum Order Quantity:1 set
Price:negotiation
Payment Terms:L/C, D/A, D/P, , T/T, Western Union
Supply Ability:10,000 sets per month
Delivery Time:7-10 working days
Packaging Details:carton/wooden case

1. System Configuration


The system consists of distribution unit, rectifier module (up to 2 sets) and 1 monitoring module. The configuration is optional, as following table:


ConfigurationRectifier ModuleMonitoring ModuleDistribution
StandardGPR4830A/BGPM48M

DC output:

40A×1 (Load);

Battery output: 40A×1 (Battery)

2. Operating Principle


Under normal conditions, every parameter of rectifier modules and distribution unit are all under control of the monitoring module, operating according to the pre-set parameter or user’s commands. If AC mains fault, the system will be powered by the battery. With the battery discharge, the terminal voltage of the battery starts to descend. When the battery voltage is under 42V±0.5V, the monitoring module reports battery under voltage alarm signal and cuts off the load output, then the power system stops working. When the external AC mains recovers, the system will resume to the normal work state. (All above monitoring data are system default values that users can reset).


Except for battery over-discharge protection, battery or load over-temperature protection is prohibitive under default, users can send command to activate or inactivate according to the demanding. When the operating temperature is 55°C or more, power de-rating will be employed by system.

3. System Properties

Input
ParameterMin.TypicalMax.UnitRemark
Input voltage range90220285VacNominal operating voltage: 100V-240V
Input frequency455065Hz
Inrush current50A

Cold start @ 25°C, 285 Vac input

Tested at full load

Power factor0.98

Output
ParameterMin.TypicalMax.UnitRemark
Output voltage rating-53.5Vdc
Output voltage range-43.2-53.5-57.6Vdc
Output current range060A176~285VAC
Ripple (Vp-p)200mvAfter 1-hour operation at low temperature, apply 0.1uF film capacitor and 10uF HF electrolyte capacitor, oscilloscope band width of 20MHz, with 20CM twisted pair.
Output efficiency90%220Vac input, rated output
82%110Vac input, 15A output
Regulation±2%
Load regulation±2%
Line regulation±1%
Output power3200W176-285V Input
1200W90-175V Input

Insulation rating
ParameterRequirementRemark
Input - output3500Vdc/10mA//1minNo flashover and breakdown, with discharge tube removed.
Input-chassis3500Vdc/10mA//1min
Output - chassis750Vdc/10mA//1min
Leakage current≤3.5mA
Insulation resistanceAt normal atmospheric pressure, relative humidity: 90%, testing voltage: 500vdc, insulation of input-output, input-ground, output-ground shall not be less than 10MΩ

Ambient requirements
ParametersMin.TypicalMax.UnitRemark
Nominal operating temp-1525+55°C
Operating temp-33+55°CStart up with full load at -40°C, normal operation, with partial degradation of performance permissible. For temperature between 55°C and 65°C, output with derating to 80%
Storage tempStorage temperature-40+70°C
Relative humidity595%Long-term operation, no condensing
Atmospheric pressure70106KPa
Altitude04000m
Cooling methodForced cooling, front-in & rear-out, the fan is located inside the front panel, with speed programmable by the temperature.
Ingress protectionThe unit can operate when the diameter of dust particle is more than 5µm, with density ≤3*104 /m3. The dust shall not be conducting, electromagnetic or corrosive.

Mechanical specifications
Dimensions (Overall)442mm×250mm×43.6mm
Weight(kg) (Overall)≤7Kg(including modules)

4. Electric Connection


Chassis connects with external electric through system interface board. As shown in figure below:



1. Bracket 2. AC input socket with three-core

3. Rectifier module 4.Monitoring module

5. Signal interface 6. Output connectors


5. Application


(1) Small scale program controlled exchanger

(2) Access network

(3) Transmission equipment

(4) Mobile communication

(5) Satellite communication ground station

(6) Microwave communication

6. Features


(1) Adoption of active power factor compensation technology with factor >0.98

(2) Wide operating range of AC input voltage: 90~285Vac

(3) Operating temperature range:-33°C~+55°C

(4) Zero current/voltage switching tech with high efficiency ≥90%

(5) Perfect battery management, battery temperature compensation, LVLD and LVBD protection, battery capacity test

(6) Hot-swappable

(7) Input over/under voltage protection

(8) Output over voltage protection

(9) Output over current protection

(10) Output short circuit protection

(11) Auto current sharing, parallel operation

(12) Embedded mounted

(13) Multiple communication ports, easy for networking and remote management


7. Packing and Shipping





Our Delivery Agent

The goods can be shipped by sea, by air, by courier, by land, by train, etc.
Besides the following delivery agent, we can also look for the delivery agent with the best price in china if you need us to do for you.



8. Our Contact Information

Mobile Phone: 0086-13752765943
Telephone: 0086-0755 66600941

Email: info@estel.com.cn

lxf.estel@hotmail.com
Skype: fiona.liang10



9. Our Partner

China Outdoor Data Cabinet Telecom Rectifier System supplier

Outdoor Data Cabinet Telecom Rectifier System

Inquiry Cart 0