Microwave Communication GPE4890A Telecom Rectifier System / High Efficiency Telecom Power System High Efficiency

Brand Name:ESTEL
Certification:ISO9001, CE, 3C, FCC, TLC
Model Number:GPE4890A
Minimum Order Quantity:1
Delivery Time:7-10 working days
Payment Terms:L/C, D/A, D/P, , T/T, Western Union
Contact Now

Add to Cart

Verified Supplier
Location: Shenzhen Guangdong China
Address: 3A-8, SHUIWAN 1979 SQUARE (PHASE II), NO. III, TAIZI ROAD, SHUIWAN COMMUNITY, ZHAOSHANG STREET, NANSHAN DISTRICT, SHENZHEN
Supplier`s last login times: within 35 hours
Product Details Company Profile
Product Details

Microwave Communication GPE4890A Telecom Rectifier System / High Efficiency Telecom Power System High Efficiency


Quick Details:


Place of Origin: Shenzhen, China (Mainland)Input Voltage: AC220V
Brand Name: ESTELOutput Voltage: DC48V
Model Number: GPE4890AOutput Current: 90A
Product Name: Telecom Rectifier SystemInput Frequency 45~65Hz
Certification: ISO9001, CE, 3C, FCC, TLCInput Current: 29.7A
Installation Mode: 19” rackPower Factor: 0.98
Application: outdoor telecom enclosure

Components:

3×30A rectifier module,

1×monitoring module,

power distribution


Payment & Shipping Terms:


Minimum Order Quantity:1 set
Price:negotiation
Payment Terms:L/C, D/A, D/P, T/T, Western Union
Supply Ability:20,000 sets per month
Delivery Time:7-10 working days
Packaging Details:carton/wooden case

1. Application


(1) Small scale program controlled exchanger

(2) Access network

(3) Transmission equipment

(4) Mobile communication

(5) Satellite communication ground station

(6) Microwave communication


2. Features


(1) Adoption of active power factor compensation technology with factor >0.98

(2) Wide operating range of AC input voltage: 90~280Vac

(3) Operating temperature range:-25°C~+55°C

(4) Zero current/voltage switching tech with high efficiency ≥90%

(5) Perfect battery management, charge&discharge management, battery temperature compensation, low voltage protection, battery capacity test

(6) Hot-swappable

(7) Input over/under voltage protection

(8) Output over voltage protection

(9) Output over current protection

(10) Output short circuit protection

(11) Auto current sharing, parallel operation

(12) Embedded mounted


3. GPE4890A System Configuration


GPE4890A consists of distribution unit, rectifier module (up to 3 sets) and 1 monitoring module. The configuration is optional, as following table:


ConfigurationRectifier ModuleMonitoring ModulePower Distribution
StandardGPR4830A1GPM48DI (With Ethernet Port)

GPE4890A:

AC Input: 40A×1;

DC Output: 40A×4 (load);

Battery Output: 70A×1 (battery)

4. GPE4890A Operating Principle


Under normal conditions, every parameter of rectifier modules and distribution unit are all under control of the monitoring module, operating according to the pre-set parameter or user’s commands. If AC mains fault, the system will be powered by the battery. With the battery discharge, the terminal voltage of the battery starts to descend. When the battery voltage is under 42V±0.5V, the monitoring module reports battery under voltage alarm signal and cuts off the load output, then the power system stops working. When the external AC mains recovers, the system will resume to the normal work state. (All above monitoring data are system default values that users can reset).

5. GPE4890A System Properties


Input
ParameterMin.TypicalMax.UnitRemark
Input voltage range90220280Vac
Input frequency455065Hz
Input current29.7A
Power factor0.98

Output
ParameterMin.TypicalMax.UnitRemark
Output voltage range-42-53.5-58Vdc
Output current range090A176~280VAC
045A90~175VAC
Ripple (Vp-p)200mvAt rated input/output, apply 0.1uF film capacitor and 10uF HF electrolyte capacitor, oscilloscope band width of 20MHz.
Output efficiency9092%220Vac input
8385%110Vac input
Regulation±1%
Load regulation±1%
Line regulation±1%

Insulation rating
ParameterMinRemark
Input - output2121Vdc/10mA//1min
Input-chassis2121Vdc/10mA//1min
Output - chassis750Vdc/10mA//1min
Insulation resistanceAt normal atmospheric pressure, relative humidity: 90%, testing voltage: 500vdc, insulation of input-output, input-ground, output-ground shall not be less than 10MΩ

Ambient requirements
ParametersMin.TypicalMax.UnitRemark
Operating temp-25+55°C≥ 55°C, output with derating power
Storage tempStorage temperature-40+80°C
Humidity1090%Relative humidity, no condensing
Atmospheric pressure70106KPa
Altitude03000m
Cooling methodForced cooling with fan

Mechanical specifications
Dimensions (Overall)482.6mm×255mm×86.1mm
Weight(kg) (Overall)

≤11kg (Inclusive of module)

≤5.175kg (Frame + Distribution, exclusive of module)



6. Installation

6.1 Dimensions Diagram

6.2 GPE4890A Installation


GPE4890A is embedded power system. First insert GPE4890A to the specified location till the system is well fixed. Keep the 4 fixing holes on the bracket in line with those on the cabinet and then screw up 4 M4 cross rounded head screws, with the spring washer and flat washer. At last finish the installation after tightening the screw.


7. Packing and Shipping




Our Delivery Agent

The goods can be shipped by sea, by air, by courier, by land, by train, etc.
Besides the following delivery agent, we can also look for the delivery agent with the best price in china if you need us to do for you.


China Microwave Communication GPE4890A Telecom Rectifier System / High Efficiency Telecom Power System High Efficiency supplier

Microwave Communication GPE4890A Telecom Rectifier System / High Efficiency Telecom Power System High Efficiency

Inquiry Cart 0