Home /Pumps & Parts /

Three Phase 24V OLTC Transformer Test Instruments

Three Phase 24V OLTC Transformer Test Instruments

Brand Name:GDZX
Certification:ISO9001
Model Number:ZXYZ-2000
Minimum Order Quantity:1Set
Delivery Time:3-20 work day
Payment Terms:L/C, T/T, Western Union, MoneyGram
Contact Now

Add to Cart

Verified Supplier
Location: Wuhan Hubei China
Address: No.1 Fenghuangyuan Second Road, Jiangxia District, Wuhan City, Hubei Province, China
Supplier`s last login times: within 1 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

Transformer Testing Equipment

Three Phase 24V Transformer On Load Tap Changer Tester

This tester is mainly used to measure the transformer on-load tap-changer transition waveform, transition time, the instantaneous transition resistance, three-phase synchronization and so on.


The instrument features highly intelligent, English menu prompts, simple operation. Instrument small size, light weight, strong anti-interference ability.

It is ideal instrument to ensure safe production and good quality in power plants units, transformer manufacturing industry.


Features
1. Large output current, light weight.
2. Open circuit voltage 28V, 1A gear for testing 10Ω transition resistance, 0.5A, 0.3A for larger transition resistance.
3. Perfect protection circuit, reliable to use.
4. Vertical chassis structure, 5.7-inch large LCD display, easy site operation.
5. U disk storage function
Technical Indicators

1. Output current: 1.0A, 0.5A, 0.3A gears

2. Resistance range: 1.0A: 0.1 ~ 10Ω; 0.5A: 5 ~ 20Ω; 0.3A: 10 ~ 40Ω.

3. Resistance measurement accuracy: ± (reading × 5% + 5 words), resolution: 0.01Ω.

4. Transition time measurement range: 1 ~ 250mS.

5. Transition time measurement accuracy: ± 1mS, resolution: 0.1mS.

6. Sampling frequency: 10K.

7. Storage: U disk storage, local storage.

8. Operating temperature: -20 ℃ ~ +50 ℃.

9. Environmental humidity: ≤ 90% RH, no condensation.

10. Working power: AC220V ± 10%, 50Hz ± 10%


China Three Phase 24V OLTC Transformer Test Instruments supplier