Add to Cart
Air-conditioning Single Phase Voltage Monitoring Relay DIN RAIL
Mount
Abrupt changes in the state of the circuit and the electromagnetic
state in the power system are the root cause of overvoltage
generation. Overvoltage is divided into two categories of external
overvoltage and internal overvoltage. Studying the causes of
various overvoltages in power systems, predicting their amplitudes,
and taking measures to limit them are prerequisites for determining
the insulation coordination of power systems, and are of great
significance for the manufacture of electrical equipment and the
operation of power systems.
Regardless of the external overvoltage or internal overvoltage, it
is affected by many random factors. It is necessary to combine the
specific conditions of the power system, obtain data through
various methods such as calculation, simulation and field
measurement, and use probabilistic statistical methods to predict
overvoltage.
For the cause of over-voltage, the power system must take
protective measures to limit the over-voltage amplitude. Such as
the installation of lightning protection lines, lightning
arresters, reactors, switch contacts plus parallel resistance,
etc., in order to reasonably implement insulation coordination to
ensure the safe operation of the power system.
The overvoltage protector is a new type of overvoltage protector,
which is mainly used to protect the insulation of generators,
transformers, vacuum switches, busbars, motors and other electrical
equipment from overvoltage damage.
♦ Features
-- Powered by the measuring circuit
-- Compatible with AC and DC supply
-- Built-in LCD and keypad afford a precise,digital setting
-- Compact modular 43mm housing
-- Adjustable over- and undervoltage threshold
-- Independent adjustable delay time for overvoltage, undervoltage
-- Adjustable reset mode:automatic reset or manual reset
-- 1 CO & 1NC contacts
-- Fault recording with last 3 faults
♦ Protective Functions
-- Overvoltage -- Undervoltage
♦ Typical Applications
• Pumps • Fans • Air-conditioning system
• Blowers • Motors • Compressors • Elevators
Approvals
• CE • CCC
♦ Technical data
Model | SVR1000/AD220 |
Measuring circuit | A1+,A2- |
Rated voltage | AC/DC110-240V,50/60Hz |
Monitoring functions | overvoltage,undervoltage |
Overvoltage setting range | AC/dc50.0-300v,5adjustbale |
Undervoltage setting range | AC/DC50.0-300V adjustable |
Voltage hysteresis | 1.0-90.0V adjustable |
Delay time for overvoltage | 0.1-999s adjustable |
Rest mode | Manual/automatic/automatic with power on delay |
Delay time for rest | 0.1-999s adjustable |
Indicators | LCD indicating voltage,operationand fault satatu |
Output contactly | 1 CO& 1NC |
Contact capacity | 6A,250VAC |
Dimensions(H*W*D) | 80*43*54mm |
Mounting | DIN rail |