Undervoltage Phase Voltage Monitoring Relay 3 Phase-rotation and phase loss monitoring relay , SPDT 380V

Brand Name:GINRI
Certification:CE,CCC
Model Number:JVR1000
Minimum Order Quantity:20Pcs
Delivery Time:1-30 days upon order quantity
Payment Terms:L/C, T/T, Western Union,Paypal
Contact Now

Add to Cart

Active Member
Address: No.337,Kaichuang Road,Baitawang Industrial Distrit, Beibaixiang Town,Yueqing City,Zhejiang Province,China
Supplier`s last login times: within 47 hours
Product Details Company Profile
Product Details

Undervoltage Phase Voltage Monitoring Relay 3 Phase-rotation and phase loss monitoring relay , SPDT 380V


Reliance on the disappearance of a current in a phase conductor of a polyphase circuit to disconnect a protected device or rely on the loss of one or more phases of a polyphase system to prevent a protection device that applies power to a protected device, also known as a protection device. Phase protector, phase loss protector.


This type of detection voltage can also be called three-phase power supply monitor, phase sequence protector, over voltage protection device, etc.) Mainly used for AC 50/60Hz, rated voltage below 460V, industrial three-phase 220V, 380V, 440V , 460V and other voltage levels of various fault detection, the three-phase input power supply voltage is too high, voltage is too low, lack of phase, phase failure, reverse phase (phase sequence), three-phase voltage imbalance, etc. to provide protection relay products Widely used in distribution boxes, central air-conditioning units, electric control boxes, power distribution cabinets, cranes, etc., such as central air-conditioning compressor protection, power monitoring of various elevators, pumps, oil pumps against phase loss, reverse phase protection, etc. An indispensable protective product that maintains the normal working voltage of the equipment during operation.


-- Built-in LCD and keypad afford a precise,digital setting-- Three-phase monitoring of phase sequence, phase loss, over- and undervoltage and phase unbalance-- Adjustable over- and undervoltage, phase unbalance threshold-- Independent adjustable delay time for overvoltage, undervoltage, phase unbalance-- Powered by the measuring circuit-- 1 NO & 1NC contacts-- Faulure recording


♦ Protective Functions

-- Phase sequence

-- Phase loss

-- Phase unbalance

-- Overvoltage

-- Undervoltage


Applications Pumps / Fans Blowers / Motors / Compressors ,have the CE CCC Certain ,make sure every product Quality ,Meet industry standards


♦ Technical data


TypeJVR1000
Measuring circuitL1,L2,L3
Rated voltage380VAC ,50Hz
Monitoring functionsphase sequence, phase loss, overvolatege, undervoltage,phase unbalance
Overvoltage setting range390-490V adjustable
Undervoltage setting range300-470V adjustable
Hysteresis10V
Delay time for overvoltage and undervoltage0.1-25s adjustable
Phase unbalance setting range5%-29% adjustable
Delay time for phase unbalance1-25s adjustable
Delay time for phase loss1s
Delay time for phase sequenceinstant
IndicatorsLCD indicating voltage,current,operation status
Output contacts1 NO,1NC
Contact capacity6A ,250VAC
Dimensions (H x W x D)80×40×54mm
MountingDIN rail

China Undervoltage Phase Voltage Monitoring Relay 3 Phase-rotation and phase loss monitoring relay , SPDT 380V supplier

Undervoltage Phase Voltage Monitoring Relay 3 Phase-rotation and phase loss monitoring relay , SPDT 380V

Inquiry Cart 0