Add to Cart
DC Output Board PLC Relay Module , 4 Channel Weidmuller Relay Board DPDT
Input and output of PLC
Input interface:
The optocoupler consists of two light emitting diodes and a
phototransistor.
Light-emitting diodes: In the optocoupler input signal changes, the
light-emitting diodes and the input signal to produce the same
change in the light signal.
Photo-electric three-level tube: It is turned on under the
irradiation of light signal, and the degree of conduction is
related to the strength of the light signal. In the linear
operating region of the optocoupler, the output signal has a linear
relationship with the input signal.
Input interface circuit working process: When the switch is closed,
the diode emits light, and then the triode is turned on under light
irradiation, and the signal is input to the internal circuit. When
the switch is off, the diode does not emit light and the transistor
does not conduct. Input signal to internal circuit. It is through
the input interface circuit to convert the external switch signal
into a digital signal that can be accepted within the PLC.
Output Interface
PLC relay output interface circuit
Work process: When the internal circuit outputs a digital signal 1,
there is current flowing through, the relay coil has current, and
then the normally open contact is closed to provide current and
voltage for load conduction. When the internal circuit outputs a
digital signal 0, no current flows, the relay coil has no current,
and then the normally open contact opens, disconnecting the load's
current or voltage. That is, the internal digital circuit is
converted into a signal through the output interface circuit to
make the load act or not.
Three types:
Relay output: contact, short life, low frequency, AC and DC load
Transistor output: no contact, long life, DC load
Thyristor output: no contact, long life, AC load
♦ Features
-- Standard DIN rain mounted
-- Status indication for each input
-- Special circuit for self anti-interference
-- Isolation for each relay channel
-- with relay base, easy to replace
♦ Typical Applications
• Micro-controller • PLC control • Servo System
• Electro-magnetic valve • DC Motors
• Home intelligent control
♦ Approvals
• CE • CCC
Model | JR-4W2/24VDC |
Output type | Weidmuller Relay |
I/O points | 2 |
Input signal | NPN and PNP compatible |
Input voltage | DC24V * DC5V,DC12V,AC110V,AC220V can be customized. |
Output voltage | AC/DC 0-250V |
Output Contacts | 2CO(DPDT) |
Contact capacity(resistive) | 5A 250VAC |
Operation voltage/Release voltage | ≥75%Un/≤10%Un |
Operation time/Release time | ≤15ms/≤8ms |
Switching frequency | 0.1Hz |
Dimensions(WxH) | 87×63mm |
Mounting | DIN rail |