Add to Cart
Professional Produce 3 Phase AC Variable Resistive 400v 300kw load
bank
Product Description
The system consists of 1 sets of AC400-300KW load bank. The system
is made up of two parts of measurement and control and load, mainly
including the tank dry type ac load, automatic data acquisition
system, automatically loading and unloading control system, the
cooling device, auxiliary control, remote control box and PC
software and so on.
Technical Parameter
Rating Voltage/Frequency | 400VAC/50Hz, 3 phase 4 wire |
Rated Power | Resistive load:300kW |
Installed Capacity | Resistive load: 300kW |
Load Step | 1,2,2,5,10,10,20,50,100,100kW min step load: 1kW |
PF(Power Factor) | 1 |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | 380VAC 50Hz |
Wire Connection | Load power supply input——Copper bar (star coupling “Y”) |
Insulation | F |
Way of Working | Continuous Working |
Casing Dimensions and Cooling | about 1460*1980*1800mm(length*width*height) Forced air cooling,Horizontal inlet air and vertical cooling |
Weight | About 750 kgs / set |
Transportation | Hoisting, there are lifting lug in top of casing, also the wheel casters can be provided |
Casing Color | Grey(RAL7035)or as you required |
Workplace | Outdoor |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤1500 meter |
Atmospheric Pressure | 86~106kPa |
Contactor | Schneider |
Fuse | DELIXI |
MCU | INFINEON |
Data processing software | Kaixiang(self-developed) |
Alloy Resistance | Kaixiang(self-developed |
Product Advangent
Our Load Bank scientific and technology level is in leading
position in this industry, besides general functions, it has
following unique advantages:
High Power Load: high load power density, large capacity of single
set, parallel running to finish super power testing, and realize
tens of megawatts of power loading
Application:
1.Manufacturers of small gas engines also use load banks to test
newly manufactured engines under various mechanical loads.
2.This is accomplished by connecting the engine to the load bank
via a device called a dynamometer.
3.engine performance is monitored and, if necessary, adjustments
are made to ensure the product performs within intended
specifications.