Add to Cart
AC220V-500kW Adjustable Load Bank With Frequency 60 HZ In High
Performance
Introduction
AC220V-500kW Adjustable Load Bank accurately test output power and
load capacity of all kinds of generators, main electrical
parameters including the dynamic parameters.
Application
1. Ups system testing
2. Load optimization in prime power applications
3. Factory testing of turbines
4. factory testing of engine generator sets
5. To reducewet stacking problems
6. Periodic excercising of stand-by engine generator sets
Technical specification
Technical Parameters | |
Rating Voltage/Frequency | 220VAC 3 phase 4 wire 60Hz, phase voltage 127VAC |
Max Load Power | Resistive Load: 500kW |
Load Step | Resistive Load:11 steps; 1, 2, 2, 5, 10, 10, 20, 50, 100, 100, 200kW |
Power Factor | 1 |
Load Tolerance(each step) | ±5% |
Load Tolerance(overall) | ±3% |
Control Power Supply | External power 220VAC 3 phase 4 wire 60Hz |
Wire Connection | Load Power Supply Input——Copper bar (star connection) |
Communication Interface | RS485 (2), RS232 (1) |
Insulation Class | F |
Working Mode | Continuous Working |
Cooling | Forced air cooling, Horizontal air intake, upwards cooling |
Transportation | Hoisting, there are lifting eyes in top and wheel castors in bottom. |
Casecolor | Orange RAL2008 and black |
Dimension | Approximately; 1550*1250*1680 (Width *Length *Height) |
Operating Environment Parameter | |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤2500 meters |
Atmospheric Pressure | 86~106kPa |
Load testing: Can load power that within the rated power, test and display
stable state 3 phases voltage, current, active power, frequency,
working time, etc of generator sets.
Load/unload with one key: Either by manual control, or software control, user can preset the
power, then press load master button. Load bank will load according
to preset power.
Control Pattern: User can choose local control and intelligent control.
Local Control: There are several power steps in panel; user can load/unload by
buttons.
Intelligent Control: Through data processing software in PC, user can make automatic
load, display, record and manage testing data, form curves and
tables, also print them.
Control Pattern interlock: There is control pattern switch, when choose one control pattern,
the other pattern is invalid to avoid the clash.
Local meter display data: Local meter can display 3 phases voltage, current, active power,
frequency and so on.