3000 KVA 4 Wire 3 Phase Load Bank , Medium Voltage Dry Type AC Load Bank

Brand Name:Kaixiang
Certification:ISO9001
Model Number:AC400-3000KVA
Minimum Order Quantity:1 set
Delivery Time:Within 30 working days
Payment Terms:L/C, T/T, Western Union
Contact Now

Add to Cart

Active Member
Location: Shijiazhuang Hebei China
Address: No33 Wangshan Road, Green Island Economic Development Zone, Shijiazhuang, China
Supplier`s last login times: within 1 hours
Product Details Company Profile
Product Details

AC400-3000KVA 3 Phase Load Bank With Blue Colour And High Performance

Product description

(1) According to the special requirements of users on site, in the agreement the technical standards of AC400-3000KVA Resistive Inductive Load Bank (hereinafter referred to as "system") and its accessories are proposed including their function, performance, usage, structure, installation and test to provide users with a high efficient and reliable choice, in order to meet the need for generator load test.

(2) The system consists of 1 sets of 3000KVA Load Bank, The resistive power is 2400kW, the inductive power is 1800KVAR. The system is made up of two parts of measurement & control and load, mainly including the medium voltage dry type AC load bank, automatic data acquisition system, automatically loading and unloading control system, the cooling device, auxiliary control, remote control box and PC software and so on.

Technical Parameter

System Parameter
Rating voltage/frequency400V, 3 phase 4 wire 50Hz
Max Load Power

Apparent Power: 3000KVA

Resistive Load: 2400kW

Inductive Load: 1800KVAR

Load Resolution

Resistive Load: 20 steps 1kW,2kW,2kW,5kW,10kW,10kW,20kW,50kW,100kW,200kW,200kW,200kW, 200kW,200kW,200kW,200kW,200kW,200kW,200kW,200kW

Inductive Load: 17 steps

1KVAR,2 KVAR, 2KVAR, 5KVAR, 10KVAR, 10KVAR, 20KVAR, 50KVAR, 100KVAR, 200KVAR, 200KVAR, 200KVAR, 200KVAR, 200KVAR,200KVAR,200KVAR,200KVAR

Power Factor0.8(lag)
Load Tolerance (each step)±5%
Load Tolerance (overall)±3%
Fan &Control VoltageExternal AC 3 phase 4 line, 380V/50Hz
Wire Connection

Load bank input——Copper bar (star coupling ”Y”)

Control power input——Connector-bar

Communication InterfaceRS485,RS232
InsulationF
Max Protection GradeIP54
Duty CycleContinuous
CoolingForced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling
EnclosureContainer type,with a ladder, air inlet and outlet with mesh enclosure and protection door
Internal LightingAdequate internal lighting will be provided
TransportationHoisting, there are lifting lug in top of casing
ColorGrey RAL7035 or as required
Dimensions6058mm×2350mm×2591mm(L×W×H)
Operating Environment Parameter
WorkplaceOutdoor
Ambient Temperature-10℃~+50℃
Relative Humidity≤95%
Atmospheric Pressure86~106kPa
Brands of Main Components
ContactorSchneider
FuseMiro
PLCSiemens
Alloy ResistorKaixiang
Data Processing SoftwareKaixiang
Product Advantage

(1) Overvoltage Protection: the input load voltage is over the safe threshold value, system unload automatically and give an alarm.

(2) Short Circuit Protection and Over Current Protection: when short circuit, fuses in the load bank can insure to unload automatically.

(3) Overheating Protection: temperature is over the safe threshold value, system unload automatically and give an alarm.

(4) Smoke Fog Protection: If there is smoke fog in the container, system cut off load automatically and give an alarm.

(5) Fan Delivery Protection: insufficient air volume with any fan 2450m³/h, system unload automatically and give an alarm.

(6) Overload protection with fan: when any fan cannot normally work, the load bank can unload automatically and give an alarm.

(7) Emergency Stop: manually press the Emergency Stop switch on the panel, then load bank is in locked state, and cannot do any operation.

(8) Protection Switch: some protection with switch, when misinformation or in special need, user can close the corresponding protection function temporarily.

(9) Safety Monitor: through indicator lights on main interface, user can monitor system state. When system abnormally stop and protect, software interface prompt the cause immediately.

Application

Large generator system testing in ocean engineering, drilling facilities,ship construction etc field
Factory testing for generator, static voltage characteristic test, speed characteristic test;
Marine generator overload protection test,parallel operation test,reverse power and reverse current protection test
Assist shipyard in mooring test,sea trial test
Assist with the acceptance of the vessel generator test

China 3000 KVA 4 Wire 3 Phase Load Bank , Medium Voltage Dry Type AC Load Bank supplier

3000 KVA 4 Wire 3 Phase Load Bank , Medium Voltage Dry Type AC Load Bank

Inquiry Cart 0