Three Phase Resistive Load Bank Black 300 KW Load Dummy Load Cabinet


Product Description


Resistive load bank is a device which can simulate the real-life resistive loads and provides a rigorous test regime for power supplies from 1kW to 60MW.The “load” of a resistive load bank is created by the conversion of electrical energy to heat by power resistors. It mainly used to test and maintenance of Engine Generators, Storage Battery Systems, UPS Systems, Inverters, Ground Power Units, Auxiliary Power Units, Aircraft Power Generators, Wind Generators, Hydro Generators etc.


Technical Parameter


Rating Voltage/Frequency400VAC/50Hz, 3 phase 4 wire, line voltage 380V, phase voltage 220V
Rated PowerResistive load: 300kW
Installed CapacityResistive load: 300kW
Load Step1,2,2,5,10,10,20,50,100,100kW, min step load: 1kW
PF(Power Factor)1
Load Tolerance(each step)±5%
Load Tolerance(overall)±3%
Display Precision0.5 class
Control PowerSingle voltage 220VAC 50Hz
Wire Connection

Load power supply input——Copper bar (star coupling “Y”)

Control power supply input——Connector-bar

InsulationF
Way of WorkingContinuous Working
Casing Dimensions and Coolingabout 1460*1980*1800mm (length*width*height) Forced air cooling,Horizontal inlet air and vertical cooling
WeightAbout 750kgs/set
TransportationHoisting, there are lifting lug in top of casing, also the wheel casters can be provided
Casing ColorGrey(RAL7035)or as you required
WorkplaceOutdoor
Ambient Temperature-10℃~+50℃
Relative Humidity≤95%
Altitude≤2500 meter
Atmospheric Pressure86~106kPa
ContactorSchneider
FuseDELIXI
MCUINFINEON
Data processing softwareKaixiang(self-developed)
Alloy ResistanceKaixiang(self-developed)


Product Advangent


(1) Communication Mode:RS485/ USB or RS232 interface for communication.

(2) Load Mode: manual load or automatic load

(3) Manual Load: input power and power factor, and load according to the preset value.

(4) Automatic Load: set several load stages and duration, then complete the process according this stages automatically. 0%- 25%,- 50%,- 75%, -100%

(5) Real-time Monitor: through software display main parameter value, such as voltage, current, power, power factor, frequency and time.


Application:


As the generator loading system
Periodic running test for standby generator
UPS inspection and maintenance
Ship battery charging/discharging system testing
The acceptance of new system and testing of servicing equipment