280KW Commerial Diesel Generators With Cummins Engine NTA855-G2A For Hotel


Genset Specifications:


Genset modelSCF350
Genset rated power280KW/350KVA
Rated voltage400/230V (adjustable)
Rated current360 Amps
Frequency50 Hz
Power factor0.8 Lagging
Connecting type3 phase 4 wire
Cooling systemClosed cycle water-cooled with fan, water tank
Overall dimension (L×W×H) mm3000×1000×1750
Gross weight (kg)3200

Engine Specifications:


Diesel Engine
BrandCCEC CUMMINS
ModelNTA855-G2A
Engine type6 cylinders in Line,4 stroke, direct injection
AspirationTurbocharged and water-to-air intercooled
Rotating speed1500 RPM
Engine cooling systemWater-cooled
Speed governing systemElectronic speed governor
Starting methodBy 24V batteries
Engine filter systemDry type air filter ,fuel filter, oil filter, water filter
Displacement(L)14
Bore×Stroke(mm)140×152
Compression ratio14.0: 1
100% Load fuel consumption (l/h)≤66.2
Lube capacity(L)36

Alternator Specifications:


Alternator
BrandFARADAY
ModelFD4LS1-4
Excite typeBrushless self-excited AVR regulation
Connecting type3 phase 4 pole
Steady frequency change0.50%
No load voltage≥95%-105%
Steady voltage≤±1%
Insulation classClass H
Protection gradeIP23

Basic components of Generator Set:

         

1. Diesel engine with 3 filters.

2. AC synchronous generator.

3. Water tank & radiator assembly.

4. The cooling fan and fan guard.

5. Heavy duty steel channel base frame.

6. Genset control system.

7. Genset circuit breaker.

8. 24V DC starting motor and charging alternator.

9. Vibration-damping supports between engine/alternator and the base frame.

10. Base fuel tank for 8 hours operation (silent type).


Standard accessory list

         

1. Fuel connecting pipes 1 set.

2. 12V DC dry type battery c/w battery cables 2 sets.

3. Industrial type silencer c/w stainless steel flexible exhaust bellows 1 set.

4. Shock absorption rubbers 6 pcs.

5. The tool kit and manuals 1 set (English version).


Operating conditions of generator set:

       

1. Altitude: ≤1500 m.

2. Ambient Temperature: -15℃~50℃.

3. Relative air humidity: ≤90%.

4. The site can't has electric conduction dust and corrosive gas that destroies metal insulation.

5. The site can't has explosion danger.