125KVA Mobile Electric Generator Powered By Cummins Engine 6BTA5.9-G2


Genset Data: 400/230V, 50Hz, 3 Phase 4 Pole, 1500RPM.


Product Description:


1. Prime power 125KVA, standby power 138KVA.
2. Powered by Cummins engine.
3. Original Engga alternator.
4. Delixi air breaker.
5. Electric start with batteries.
6. Base integrated fuel tank.
7. Smartgen controller.

8. ATS is for option.


Genset Specifications:


Genset modelSCE125
Genset rated power100KW/125KVA
Rated voltage230/400V (adjustable)
Rated current180 Amp
Frequency50 Hz
Power factor0.8 Lagging
Connecting type3 phase 4 wire
Cooling systemClosed cycle water-cooled with fan, water tank
Overall dimension (L×W×H) mm4150×1600×1800
Gross weight (kg)2000

Engine Specifications:


Diesel Engine
BrandDCEC CUMMINS
Model6BTA5.9-G2
Engine structure6 cylinders vertical in line, 4 stroke, turbocharged
Rotating speed1500 RPM
Engine cooling methodWater-cooled
Speed governing systemElectronic speed governor
Starting methodBy 24V batteries
Engine filter systemDry type air filter ,fuel filter, oil filter, water filter
Displacement(L)5.9
Bore×Stroke(mm)102×120
Compression ratio17.5: 1
100% Load fuel consumption (litre/h)≤24.8
Lube capacity(L)16.3

Alternator Specifications:


Alternator
BrandENGGA
ModelEG225-100N
Excite typeBrushless self-excited AVR regulation
Connecting type3 phase 4 pole
Steady frequency change0.50%
No load voltage≥95%-105%
Steady voltage≤±1%
Insulation classClass H
Protection gradeIP21

INSPECTION AND TEST


1 GENERAL

1.1 Each engine shall be tested at manufacturer’s workshop to certify the engine output and fuel consumption in accordance with the site operating condition specified by purchaser on the specification datasheet.

1.2 All relevant information drawings pertinent to the testing and test procedure shall be transmitted to the purchaser in advance of the test date notification.

1.3 The purchaser shall call for additional testing if test results are unsatisfactory or marginal. Any equipment rejected shall be repaired or replaced to the purchaser’s satisfaction and tests shall be repeated.

1.4 Any unsatisfactory material, equipment, installation, or workmanship shall be replaced or repaired to the purchasers satisfaction at the manufacturers cost.

1.5 The engine and generator shall be tested individually in accordance with relevant standards specified above.

1.6 The completed and individually tested engine and generator shall be assembled onto the base plate with all auxiliaries, instruments and controls for a complete test of the generator set.


Invitation to visit our factory

  1. If you are interested in our products we sincerely invite you to take a visit of our factory when you are in China.
  2. Our factory locates in Foshan City, which is famous for its ceramics, is just 45 minutes away from Guangzhou, and 35 minutes away from Canton fair.
  3. When you come to Guangzhou or Canton fair, we can send cars to pick you up and take you to our factory.
  4. In the factory we can discuss more about the cooperation and we will listen to your requirements.
China 125KVA Mobile Diesel Generators Powered By Cummins Engine 6BTA5.9-G2 supplier

125KVA Mobile Diesel Generators Powered By Cummins Engine 6BTA5.9-G2

Inquiry Cart 0