3 Phase 4 Wire Open Diesel Generator 400KW / 500KVA Cummins KTA19-G3A

Brand Name:SHX
Certification:ISO9001:2015, CE, TUV, BV
Model Number:SCE500B
Minimum Order Quantity:1 Set
Delivery Time:20 working days
Payment Terms:L/C, T/T
Contact Now

Add to Cart

Active Member
Location: Foshan Guangdong China
Address: No. 1, Xinglong 2nd Road, Guanglong Industrial Zone, Chencun Town, Shunde, Foshan, China.
Supplier`s last login times: within 35 hours
Product Details Company Profile
Product Details

3 Phase 4 Wire Open Diesel Generator 400KW / 500KVA Cummins KTA19-G3A


Features


  1. Universal design and manufacture
  2. Most widely used around the world
  3. With most service terminals
  4. Engineers are familiar with Cummins powered gensets
  5. You could find spare-parts very easy

Genset Specifications:


Genset modelSCE500B
Genset rated power400KW/500KVA
Rated voltage400/230V (adjustable)
Rated current900 Amps
Frequency50 Hz
Power factor0.8 Lagging
Connecting type3 phase 4 wire
Cooling systemClosed cycle water-cooled with fan, water tank
Overall dimension (L×W×H) mm3300×1250×1850
Gross weight (kg)4670
Diesel Engine
BrandCUMMINS
ModelKTA19-G3A
Engine type6 cylinders in Line,4 stroke, direct injection
AspirationTurbocharged and air-to-air aftercooled
Rotating speed1500 RPM
Engine cooling systemWater-cooled
Speed governing systemElectronic speed governor
Starting methodBy 24V batteries
Engine filter systemDry type air filter ,fuel filter, oil filter, water filter
Displacement(L)19
Bore×Stroke(mm)159×159
Compression ratio13.9: 1
100% Load fuel consumption (l/h)≤95.1
Lube capacity(L)38
Alternator
BrandENGGA
ModelEG315-400N
Excite typeBrushless self-excited AVR regulation
Connecting type3 phase 4 pole
Steady frequency change0.50%
No load voltage≥95%-105%
Steady voltage≤±1%
Insulation classClass H
Protection gradeIP21

INSPECTION AND TEST


1 GENERAL

1.1 Each engine shall be tested at manufacturer’s workshop to certify the engine output and fuel consumption in accordance with the site operating condition specified by purchaser on the specification datasheet.

1.2 All relevant information drawings pertinent to the testing and test procedure shall be transmitted to the purchaser in advance of the test date notification.

1.3 The purchaser shall call for additional testing if test results are unsatisfactory or marginal. Any equipment rejected shall be repaired or replaced to the purchaser’s satisfaction and tests shall be repeated.

1.4 Any unsatisfactory material, equipment, installation, or workmanship shall be replaced or repaired to the purchasers satisfaction at the manufacturers cost.

1.5 The engine and generator shall be tested individually in accordance with relevant standards specified above.

1.6 The completed and individually tested engine and generator shall be assembled onto the base plate with all auxiliaries, instruments and controls for a complete test of the generator set.


OEM Service:


Sunkings Electric Co., Ltd. Can provide professional OEM Service for customers.

  1. Unique design and manufacture of generator according to customers requirement.
  2. Customer logo printing or painting on the genset.
  3. Installation and Operation manual neutral or headings can be design according to customer requirement.
  4. Full warranty cover to support the customers.

Picture show:



China 3 Phase 4 Wire Open Diesel Generator  400KW / 500KVA Cummins KTA19-G3A supplier

3 Phase 4 Wire Open Diesel Generator 400KW / 500KVA Cummins KTA19-G3A

Inquiry Cart 0