1. Products Overview:


Our WD series power factor meter are electric unit measuring instruments, which are able to measure power factor in transmission & distribution power system, widely used in power transforming, distribution automation, intelligent building and power monitoring.


2. Technical Parameters:


Technical IndexValue
Input
Nominal valueVoltage AC:100V,220V,380V; Current AC: 1A/5A
OverloadContinuous: 1.2 time/1s; Instant: 10 time/1s
Frequency45-65Hz
Consumption<0.5VA
Accuracy0.2%
Function
DisplayLED or LCD
CommunicationRS485,Modbus-RTU protocol
AlarmOne channel passive relay; Contact capacity: 3A/30VDC,3A/250VAC, high, low, unbalance alarm etc.
Analog
DC4-20mA, DC0-20mA(Load<500Ω), DC0-5V(Load >1kΩ)
Input: 2-4 channel dry contacts, power inside, optocoupler insolation
Output: 2 switch output,normal open contact of relay
Contact capacity: 3A/30VDC,3A/250VDC
Power Supply
Voltage RangeAC/DC85-270V
Power consumption<5VA
Insulation resistance≥100MΩ
Power Frequency
Withstand Voltage
2kv/1min
Environment
TemperatureOpertation: -25-55℃, Storage: -20℃-75℃
Humidity≤93RH, no condensation, without corrosive
Attitude≤2500m

4. Main Features:


  • High-precision measurement of power meter
  • Active power display, the local data query
  • The current transformation ratio programmable settings
  • Support for RS-485, Modbus-RTU Protocol
  • Support the switch quantity input. digital output, analog output quantity transducer
  • Auxiliary power supply: ACDC 80V-270V,AC220V,AC380V,AC100V,DC48V,DC24V
  • Choose a variety of profiles, meet the requirements of different Cabinet electrical circuits.

5. Wiring Diagram



6. Options:



7. RS485 Communication data:


  • Protocol: Modbus RTU
  • Bus Type: RS485
  • Baud Rate: 2400/4800/9600(deffault)
  • Address Range: 1~247
  • Communication Distance:1000M
  • Parity:EVEN(default)/ODD/NONE
  • Data Bit:8
China Iso9001 Three Phase Digital Power Factor Meter Active Power Display High Precision supplier