Add to Cart
KAN109 Carbon Monoxide Gas Detector for Underground Garages
Product Introduction
The detector has a full - temperature compensation function, which automatically corrects the impact of temperature changes on the detected concentration. The bus is equipped with an anti - interference and anti - static protection circuit to ensure the long - term stable operation of the detector. The detector uses a high - precision electrochemical gas sensor, which features high sensitivity and strong anti - interference ability. When the detector alarms, it can emit audible and visual alarm signals. It can optionally be equipped with a linkage output node, which can be connected to a DC12V pulse gas solenoid valve or a dry - contact output.
Product Description
Detection Principle | Detection Range and Sampling Method | Detection Range | Alarm Method |
Electrochemical (for CO), Infrared (for CO₂) | Diffusion type for carbon monoxide and carbon dioxide | 0 - 500PPm (CO), 0 - 5000PPm (CO₂) | Audible and visual alarm |
Operating Voltage and Power | Installation Method | Alarm Output | Ambient Air Pressure |
DC24V ± 6V ≤ 1.5W during normal monitoring ≤ 3W in alarm state | Wall - mounted installation, Ceiling - mounted installation | Optional 1 set of DC12V pulse solenoid valve output (discharged by 1000μf capacitor) or a set of passive relay output | 86KPa - 106KPa |
Response Time and Recovery Time | Operating Temperature and Humidity | Specification | |
≤ 30 seconds | -10°C - +55°C, ≤ 93%RH | ABS plastic, ≤ 150g, 108×95×45 |