1. Product Overview
Radar level sensor antenna emits and narrow microwave pulse. This pulse propagates in space at the speed of light. When it encounters the surface of the measured medium, part of its energy is reflected back and received by the same antenna. The time interval between the transmitted pulse and the received pulse is proportional to the distance from the antenna to the surface of the measured medium. The 80GHz intelligent series radar level gauge is suitable for non-contact continuous measurement of the level of liquid, slurry, granular material and block material. Applicable In the occasions where temperature and pressure change greatly, inert gas and volatilization exist.
The hardware system uses advanced microprocessors and embedded
system processing software. The signal algorithm processing
integrates advanced Echo-capture signal processing technology. This
makes the product applicable to various complex industrial plant
conditions.
The “empty tank pretreatment” technology enables the instrument to
correctly identify effective echoes and obtain correct measurement
results even in the presence of multiple false echo interference.
Not affected by various complicated working conditions. Such as
strong surface fluctuations, foam, moisture and dust interference.
2.Product Introduction
Model KLD803 |
3.Technical Specifications
Transmission Frequency | 76GHz~81GHz |
Measuring Range | 0~120m (liquid) |
Measurement Accuracy | ±2mm |
Beam Angle | 3°/6° |
Range Of Dielectric Constant Used | ≥2 |
Power Supply Range | DC24V/AC220V 2-wire system/4-wire system/6-wire system |
Communication Mode | MODBUS bus HART |
Signal Output | 4~20mA+RS485 4~20mA |
Fault Output | 3.8mA, 4mA, 20mA, 21mA, hold |
Field Operation/Programming | 128 × 64 dot matrix display/4 buttons can be equipped with host setting software |
Industrial Temperature/Humidity | T0:-40~85℃/≤95%RH;T1:-40~200℃; T2:-40~500℃; T3:-40~1000℃ |
Shell Material | Cast aluminum, stainless steel |
Antenna Type | Lens antenna |
Process Pressure | -0.1~2.5MPa |
Cable Entry | M20 * 1.5 or 1/2NPT |
Recommended cable | AWG18 or 0.75mm ² |
Degree of protection | IP67 |
Explosion proof grade | Exd IIC T6 Gb |
Installation method | Thread or flange |
Net weight/gross weight | Random configuration |
Packing box size | Random configuration |
Transmission frequency | 76GHz~81GHz |
4.Structural dimensions
Schematic Diagram of Pipe Thread Process Connection Structure Size at Room Temperature
5. Installation
Two points for installation:
(1) Align the target material level to ensure that it is
perpendicular to the material level plane;
(2) Avoid false echoes. See the following points for typical
working conditions.
● Ensure that there are no interfering objects, such as ladders and
steps, within the beam range.
Figure 5 – 1 Schematic Diagram of Instrument Installation Position
● The instrument installation shall ensure that the antenna beam avoids the feed inlet, as shown in Figure 5-2.
Figure 5 – 2 Antenna beam avoiding feed inlet
● The instrument shall be installed at least 20cm away from the
vessel wall, otherwise it is likely to produce wrong readings, as
shown in Figure 5-3.
Remarks: The liquid measurement installation spool should be
perpendicular to the ground.
Figure 5 – 3 Installation at least 20cm away from the vessel wall
● The solid cone container shall ensure that the beam is directed at the tank bottom as much as possible, otherwise the measurement results at the tank bottom may be inaccurate, as shown in Figure 5-4.
Figure 5 – 4 The conical tank shall ensure that the beam is directed at the tank bottom as far as possible.
6. Product wiring diagram
6.1 Wiring diagram of single chamber enclosure 24VDC power supply
four wire products
Fig. 6-1 Wiring Diagram of Four wire Products
In four wire system application, 4-20mA analog output is two
separate terminals except 24V power supply terminal. At the same
time, the four wire system also provides 485 output terminals,
which is convenient for connection and debugging with PC or the
site requiring 485 interface.
6.2 Wiring diagram of single chamber enclosure 24VDC power supply two-wire product
Fig.6-1 Wiring diagram of two-wire products
In the two-wire system application, in addition to the traditional power supply terminal (4-20mA output), the instrument also has a serial communication terminal, which is convenient to connect with the current mainstream IOT equipment or transparent transmission equipment for remote control and debugging.
Model Selection Table
80GHz FM radar level meter
Model | Model KLD801 |
Licence | P Standard type (non explosion proof) I Intrinsically safe(Exia IIC T6 Ga) D Flameproof type(Exd IIC T6 Gb) |
Process connection | B Flange DN80/304 C Flange DN100/304 D Flange DN125/304 E Flange DN150/304 Y Special customization |
Antenna type/material | P 78mm Lens antenna Y Special customization |
Process temperature | V Standard/(-40~120℃) Y Special customization |
Electronic unit | 2 (4-20)mA/24V DC Two wire 3 (4-20)mA/24V DC/HART Two wire 4 (4-20)mA/220V DC Four wire 5 RS485/Modbus/24V DC Four wire 6 (4-20)mA/RS485 /24V DC Six wire dual output |
Enclosure/degree of protection | L Aluminium/IP67 Single cavity B Aluminium/IP67 Double cavity J stainless steel 304/IP68 Single cavity |
Cable incoming line | M M20*1.5 N ½NPT |