Low Temperature Heat Pump Cooling System / Portable Heat Pump Air Conditioning System

Brand Name:Yushen
Certification:CCC, ISO, CQC
Model Number:SDLC-063Y
Minimum Order Quantity:1 set
Delivery Time:1-2weeks
Payment Terms:T/T
Contact Now

Add to Cart

Active Member
Location: Shanghai Shanghai China
Address: Foreign sales office: 588 South Qilianshan Road ,Putuo area, Shanghai,China
Supplier`s last login times: within 27 hours
Product Details Company Profile
Product Details

Low Temperature Heat Pump Cooling System / Portable Heat Pump Air Conditioning System


Heat Pump Cooling System Features


(1) The air source heat pump system is a combination of cold and heat sources. There is no need to set up a special freezer room or boiler room. The unit can be placed on the roof or the ground at will, without occupying the effective use area of he building. The construction and installation is very simple.

(2) The air source heat pump system has no cooling water system, no cooling water consumption, and no power consumption of the cooling water system. In addition, there have been many reports of Legionella infections caused by cooling water pollution. From the perspective of safety and hygiene, considering air source heat pumps also has obvious advantages.


Heat Pump Cooling System Advantages

  • Bigger fan, large air volume and higher heat exchanger efficiency
  • Mutiple throttle channel, more acurate control of refrigerant quanity, saving operation cost
  • Yushen air-source Cooling equipment is 40% energy-saving than that of AC unit in general .
  • Industrial leading shell and tube heat exchanger in the water side

Heat Pump Cooling System Technical data


ModelSDLC-063Ycode name.pdf
Compressor capacity25HP
FunctionCool
Electricity380V 3N-50Hz
Working conditions-25~+45
DataCoolaNominal capacityKW63
Input powerKW20.1
COP/3.13
A35W0bKW/COP48.58/2.79
A35W-5KW/COP41.26/2.51
A35W-10KW/COP34.72 /2.17
A35W-15KW/COP29.06/1.91
Max. running currencyA56
Compressor quantitySet2
Refrigerant/charging quantity kg/R22/15*2
Air blow type/Top
Water pipe diametermm50
Rating flowm³/h12.6
Water side pressure losskPa≤45
Noise leveldB(A)62
Overall dimensions(L×W×H)mm2100×1100×2080
Weightkg730

a:Nominal Cooling conditions: ambient dry bulb temperature35℃, , outlet water temperature 7℃, water flow 0.172 * nominal cooling capacity

b:A7W35 working condition: inlet air temperature 35℃, outlet water temperature 0℃


Heat Pump In Cold Weather Applications

  • Cooling for any indoor air conditioning conditions such as office building, hotel, school, home.
  • Produce cool water for factory use

More about ASHP

  • Green and environmental protection: The air source heat pump absorbs heat from the natural air of the surrounding environment and has little impact on the environment. It is a true environmental protection equipment.
  • Safe and comfortable: the water tank and the main unit are completely separated and have reliable safety. A variety of terminal options for customers to enjoy
  • Easy to install: the unit can be installed outdoors, such as in open spaces such as roofs and floors. It has a small footprint and is easy to install. It does not need to set up a machine room to save space.
China Low Temperature Heat Pump Cooling System / Portable Heat Pump Air Conditioning System supplier

Low Temperature Heat Pump Cooling System / Portable Heat Pump Air Conditioning System

Inquiry Cart 0