IEC60950 Open Loop Hall Effect Current Sensor High Accuracy Switched Mode Power Supplies

Brand Name:TOKEN
Certification:CE;ROHS
Model Number:TKC-H
Minimum Order Quantity:10pcs
Delivery Time:7~10 working days
Payment Terms:L/C, T/T, D/P, Western Union
Contact Now

Add to Cart

Active Member
Address: NO.80,FEITIAN AVENUE,INDUSTRIAL CLUSTER LUKOU TOWN
Supplier`s last login times: within 39 hours
Product Details Company Profile
Product Details

Switched Mode Power Supplies Open Loop Hall Effect Current Sensor


TKC-H series is a kind of dismountable current sensor, which is a open loop device based on the measuring principle of the hall effect ,with a galvanic isolation between primary and secondary circuit .It provides accurate electronic measurement of DC,AC or pulsed currents.


Open-loop current sensors measure AC and DC currents and provide electrical isolation between the circuit being measured and the output of the sensor (the primary current is measured without electrical contact with the primary circuit, providing galvanic isolation).


Standards


  • UL94-V0.
  • EN60947-1:2004
  • IEC60950-1:2001
  • EN50178:1998
  • SJ 20790-2000

Electrical data(Ta=25℃±5℃,RL=2KΩ,CL=10000PF)



Type

Parameter

TKC600HTKC1200HTKC1800HTKC2400HTKC3000H

Unit


Rated current(Ipn)

±600±1200±1800±2400±3000A

Measuring range(Ip)

±1200±2400±2700±3600±4500A

Rated output voltage

@Ip=±Ipn ±4±1%V

Supply voltage

±15±5%V

Power Consumption

+25,-10mA

Offset voltage

@Ip=0 ±20mV

Magnetic offset

@Ip=±Ipn-0 ±20mV

Offset voltage drift

@ -40~+85℃ ≤±1mV/℃

output drift
@ -40~+85℃ ≤±1mV/℃

Linearity

@Ip=0-±Ipn ≤1%FS

Response time

@50A/μS, 10%-90% ≤7μS

Galvanic isolation

@ 50HZ,AC,1min 6KV

Applications


Variable speed drives

Welding machine

Battery supplied applications

Uninterruptible Power Supplies (UPS)

Electrochemical


Mechanical dimension(for reference only)



Remarks:

1. All dimensions are in mm.

2. General tolerance ±1mm.


Directions for use


When the current will be measured goes through a sensor, the voltage will be measured at the output end.

(Note: The false wiring may result in the damage of the sensor)

The output amplitude of the sensor can be adjusted according to users’ requirements.

Custom design in the different rated input current and the output voltage are available.


General date


ValueUnitSymbol
Operating temperature-40 to +85ºCTA
Storage temperature-40to +125ºCTS
Mass(approx)602gM

Characteristics chart


Effects of impulse noise


China IEC60950 Open Loop Hall Effect Current Sensor High Accuracy Switched Mode Power Supplies supplier

IEC60950 Open Loop Hall Effect Current Sensor High Accuracy Switched Mode Power Supplies

Inquiry Cart 0