TSTLP SMT-ESE40 controlled ese air terminal for lightning protection


  • Special Technical Parameters


SMT-ESE40 ese air terminal for lightning protection
Patent RightAvailable on request
CE CertificationsNr WTS16030019S (Ref Standard EN 60060-1:2010)
Relevant STANDARDS
NF C 17-102:2011
UNE 21.186:2011
IEC 60060-1:2010
GB/T T16927.1-2011

  • SMT-ESE40 Radius Protection as per different protection levels


For each of the lightning protection levels, a minimum current level to be protected against has been determined (selected). Table 5 details these current levels, together with probability percentages that lightning may be greater than these levels. For example, Lightning Protection Level I positions terminals such that 99% of all lightning flashes are intercepted (all those of 3 kA or greater). There is only a 1% probability that lightning may be smaller than the 3 kA minimum, and may not be close enough to an air-terminal to be intercepted. It should be noted that flashes of less than 3 kA are rare, and typically would not be expected to cause damage to the structure. Protection greater than Lightning Protection Level I (99%) would require significantly more material, is not covered by the standard and generally is not required for commercial construction.


Minimum current levels (related to interception efficiency) for lightning protection levels 1 to 4

Protection LevelsLEVEL 1LEVEL 2LEVEL 3LEVEL 4
Minimum current (kA)351016

Probability current is greater

than minimum (%)

99979184
Rolling sphere radius (m)20304560

The lower lightning protection levels (LPL 2 , 3 & 4) each increase the air terminal spacing, reducing their ability to capture smaller lightning flashes, thus reducing overall the percentage of lightning events they can protect against.


  • TSTLP ESE Air Terminal Protection of high rise buildings (height greater than 60 m)

Additional protection against direct lightning strike for the highest 20% of the structure height for buildings greater than 60 m or any point above 120 m, using ESE Air Terminal or any other means must be implemented at each façade wall according to a valid standard. Furthermore a minimum of 4 Down conductors, interconnected by a ring conductor when applicable, shall be used, distributed along the perimeter and if possible at each angle of the building.

NOTE: in general the risk due to the lateral flashes is low because only a few percent of all flashes to tall structures will be to the side and moreover their parameters are a lot lower than those of flashes to the top of structures.


  • SMT-ESE40 ese air terminal for lightning protection installation photo


PDF Datasheet Download - TSTLP SMT-ESE40.pdf


Tag: ese air terminal, air terminal for lightning protection

China 40 μs Triggering Time Controlled ESE Air Terminal For Lightning Protection supplier

40 μs Triggering Time Controlled ESE Air Terminal For Lightning Protection

Inquiry Cart 0