Product Details
Fixed Type Innovating Aerosol Extinguishing Systems Eco-friendly
Clean Agent
Brief requirements of Aerosol Extinguishing Systems according to
GA499.1-2010
- Spray process and state-fire extinguishing device should be able to
spray normally after switching on the start signal
- During discharge, there shall be no open fire or spark at the
nozzle, and no residue shall overflow during or after injection
- After the completion of spraying, the shell shall not be deformed,
burnt through or ignited on the surface of the shell.
- The total filling mass of aerosol generator in a fire extinguishing
device shall not be more than 10kg, and the deviation of filling
mass shall not exceed 2% of its nominal mass.
- The operating voltage of the electric initiator shall not be
greater than 24 vd.c.
- The raw materials used to produce aerosol generating agents should
be non-toxic to organisms and the combustion products do not
contain harmful ingredients that damage the atmospheric ozone
layer.
Fireless 125 technical parameter:
Item | Specification |
Overall dimensions(mm) | 240( diameter)X126(height) |
Extinguishing device weight(Kg) | 6.8 |
Agent quantity(Kg) | 3.5 |
Protected volume(m³) | 125 |
Working temperature(℃) | -50℃~+95℃ |
Safety current(mA,DC) | ≤150mA |
Discharge times) | ≤ 19 |
Service life(year) | 10 |
FAQ for technical terms
- Do the protected area needed 100% closed?
Answer: no, it doesn’t .
- what is ratio of open area to total area in enclosure?
Answer:Represents the unsealing degree of the enclosed space, and
its value is the ratio of the unclosed open area in the enclosed
space to the total surface area, expressed as a percentage.
- What is flame extinguishing density?
Answer:The mass of an aerosol agent required to extinguish a fire
in unit volume, g/m³.
- What is discharge delay time?
Answer:The time when the fire extinguishing device receives the
starting signal and the nozzle begins to spew hot gas sol
extinguishing agent.
- What is discharging time?
Answer:The time from the beginning discharging aerosol to
discharging stopped.
- What is outlet temperature in discharging?
Answer:During the process of discharge heat aerosol fire
extinguishing agent, the outlet temperature is where 5 meters away
from nozzle.
- Is there any cooling equipment in the generator?
Answer:Yes, it’s medium or device installed in a fire extinguishing
device to effectively reduce the temperature of a hot gas aerosol
extinguishing agent before it passes through the nozzle.
Application:
data centers/ UPS/ ESP/ museums/ warehouses/ electric cabinets/
generator rooms panels/ engine rooms/ different transportation
vehicles
Company Profile

ABOUT US
NOVTEC means “Technology &Innovation”. It is the company behind
FireLess.
Fireless is developped from Chinese Military Smoke technology and
now it is a transformation from military product to civil field. As
one of the latest generation of high efficient fire extinguishing
product, it is suitable for electric power, new energy vehicles,
underground tunnel, wind power filed, chemical engineering,
communication and other industry filed that could not use water,
foam and powder fire extinguishers, and possesses advanced
technical level in the world.Fire and Explosion Protection Systems
for the military forces are manufactured to stringent standards and
undergo comprehensive testing to ensure reliable operation in the
most difficult and hazardous environments imaginable.

WHAT IS FIRELESS AEROSOL TECHNOLOGY?
There is a revolution which is taking place in fire suppression.
FireLess is a leading manufacturer of highly innovative condensed
aerosol fire-extinguishing devices, which can be used for many
kinds of fires extinguishing and suppression. It is a technology
developped from military smoke technology. We are focused on
producing and developing rapid, efficient, safe, long-lasting
effective and environment protection aerosol fire extinguishing
devices.With over 10 years of experience in the China military
market, the company offer clients the globally best products and
solutions based on strong military technology. The technical team
are military fire protection professionals and innovators who are
convinced FireLess is best way to safeguard people, property and
protect environment.


FIRELESS EXHIBITIONS
Demestic Fire Expo/ 2019 Dubai Intersec

FIRELESS CERTIFICATES
Fireless passed all necessary tests in China, and it's only brand
for military technology aerosol fire extinguishers.
Certificates:
CERTIFICATE OF TYPE APPROVAL FOR MARINE PRODUCT
(TFRI)NATIONAL CENTER FOR FIRE ENGINEERING TECHNOLOGY
(https://www.china-ncfe.cn/)
(CNCF) CHINA NATIONAL CENTER FOR QUALITY SUPERVISION AND TEST OF
FIXED FIRE-FIGHTING SYSTEMS AND FIRE RESISTING BUILDING COMPONENTS
(https://www.cncf.com.cn)
MA/ AL/ ILAC-MRA/ CNAS L0988
Fireless achieved couples of China National Invention Patent and Utility Models for both agent and appearance.

NOVTEC COMPANY CULTURE
The company is dedicated to obtaining additional international
approvals and serving global customers.
Our mission: Offer the world first class fire-extinguishing product and service
Our core value: Serve customers with honor

OUR OFFICES