108kVA 27kV 100kV Series Resonant Test System

Brand Name:Fanke High-voltage
Certification:ISO9001
Model Number:FKTF-108kVA/27kV;100kV
Minimum Order Quantity:One unit
Delivery Time:25-30 Work Days
Payment Terms:T/T
Contact Now

Add to Cart

Active Member
Location: Wuhan Hubei China
Address: Layers Building 2,N0.2-2 Guannan Science&Technology Industrial Park, East Lake High-Tech Development Zone,Wuhan ,China
Supplier`s last login times: within 39 hours
Product Details Company Profile
Product Details

Series resonance test device


1. Subject
1.10kV/300mm2 cable, unit length capacitance 0.37uF/km, cable length 1.4km, tested cable capacitance 0.153uF, test frequency 30-300Hz, test voltage 52kV, withstand voltage time 60min;
2. 35kV power transformer power frequency AC withstand voltage test, capacitance ≤0.02uF, test frequency 45~65Hz, test voltage not exceeding 68kV, test time 1min;
3. AC withstand voltage test for switches and transformers with voltage levels of 35kV and below, the test frequency is 30-300Hz, the test voltage does not exceed 100kV, and the test time is 1min;
2. Environmental conditions for device use
1. Ambient temperature: -5℃—45℃;
2. Relative humidity: ≤90﹪, no condensation;
3. Altitude: ≤1000m.
3. The main technical parameters and functions of the system
1. Rated capacity: 108kVA;
2. Rated voltage: 27kV; 100kV;
3. Rated current: 4A; 1A;
4. Power supply: single-phase 220V±10﹪;
5. Working frequency: 30-300Hz;
6. Frequency resolution: 0.1Hz; frequency instability: ≤0.1%;
7. Working time: 15min continuous operation is allowed under rated power;
8. Temperature rise: After 15 minutes of continuous operation at rated power, the temperature rise of each part of the device is ≤65K;
9. Output waveform: sine wave, waveform distortion rate <1%;
10. Quality factor: the device itself Q≥30 (when f=45Hz);
11. Protection: with over-current, over-voltage and flashover protection (see the frequency conversion power supply section for auspiciousness);
12. System measurement accuracy: effective value 1.5.


Configuration equipment list

numberEquipment nameModels and SpecificationsunitQuantity
Frequency PowerFKVF-6kW/220Vstation1
Excitation transformerCQSB(J)-6kVA/1.5×4kV/0.225kVstation1
Dry reactorCHX(Jf)-27kVA/27kVSection4
Capacitor voltage dividerTRF-100kV/150pFstation1
Compensation capacitorBWF-100kV/14.5nfstation1
Insulation supportset1
Equalizing ringset1
Wiringset1
China 108kVA 27kV 100kV Series Resonant Test System supplier

108kVA 27kV 100kV Series Resonant Test System