Product Details

Mutual Inductor Multi-function Tester , CT/PT Excitation Characteristics Tester


I. Product Description


FKFA-II Mutual Inductor Multi-function Tester is applied for measuring CT/PT volt-ampere characteristic, 5%, 10% and 15% error curve, ratio, polarity, angle error, ratio error, secondary DC resistance and secondary load, secondary loop, secondary withstand voltage and function of demagnetization. It has 600A and 2500V output.


II. Main Performed Test items:

  • CT/PT Excitation characteristics test, 5%, 10% and 15% error curve
  • CT/PT Ratio, polarity , secondary winding resistance test
  • CT/PT Secondary load, ratio error and phase angle error
  • Has the function of demagnetization
  • 600A large current and 2500V max. output

III. Technical features


1. Full-function, can test CT/PT -ampere characteristic, 5%, 10% and 15% error curve, ratio, polarity, voltAngle error, ratio error, secondary DC resistance and secondary load, secondary loop, secondary withstand voltage and function of demagnetization.

2. 600A max. current output , max. test voltage up to 2500V.

3. With a large storage capacity, 2000 sets of test data can be stored and the data will never be lost.

4. Automatic calculating knee point, with test data printing function.

5. The output of the device is all real voltage and current under the standard sine wave at 50Hz, which can effectively simulate the actual state of the tested transformer.


IV. Test data


Input voltage

Maximum output voltage

Maximum output current

Power

measurement accuracy

CT volt-ampere output

220V0—2500V15A3KVA< 0.5%

CT ratio output

220V0-8V0—600A/1000AOptionalnone< 0.5%

CT ratio measurement

The maximum ratio display: 999.9K: 5 / 1

< 0.5%

PT ratio measurement

The maximum ratio display:999.9K:100,150,100/3,100/

< 0.5%

DC resistance measurement

The maximum resistance measurement: 0.1-20Ω

Less than 1Ω:3%

More than 1Ω: <1%

angular phase difference

Minimum display: 0.01’ Accuracy::±10’

Ratio Difference

Minimum display: 0.01%

Accuracy:<0.5%

The secondary load test

Output Current: 0-200A

Time:1~5mins

The secondary withstand voltage

output Voltage: 0-2500V

Time:1~5mins

Working temperature

-10~55℃

Working voltage

AC220V(±20%)50HZ

Host volume

420×300×270

Host weight

26Kg