Home /Switching Power Supply /

Eltek Flatpack2 Rectifier 48-60/2000 HE 5G Network Equipment Doc 241115.705.DS3 - V9

Eltek Flatpack2 Rectifier 48-60/2000 HE 5G Network Equipment Doc 241115.705.DS3 - V9

Brand Name:Eltek
Certification:CE, RoHS
Model Number:241115.705
Minimum Order Quantity:1 set
Delivery Time:within 10 days of payment
Payment Terms:L/C, T/T
Contact Now

Add to Cart

Site Member
Location: Wuhan Hubei China
Address: Room B813,No.61, Yejin Avenue, Qingshan District,Wuhan City, Hubei Province, China.
Supplier`s last login times: within 1 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

Eltek Flatpack2 Rectifier 48-60/2000 HE Doc 241115.705.DS3 - v9


High efficiency and reliable rectifier/converter


The most efficient power conversion module in the industry! Since the launch the Flatpack 2 family has expanded into a wide selection of power ratings and voltages.

The Flatpack2 48-60/2000 HE is a cost efficient rectifier for 48V and 60V lead acid battery systems as well as 48V NiCad.


Applications


TELECOM

Radio base stations / Cell sites

LTE / 4G / WIMAX

Distributed Antenna Systems

Microwave / Broadband

Central office

POWER UTILITIES

Control & protection

SCADA

Communications equipment

RAIL & METRO

Control & protection

Signaling

MARINE & OFFSHORE

Communications on ships


Key Features


High Efficiency – 96.2 %

Proven Reliability

High Power Density

Application Flexibility, 2kW To Multicabinet Installations

Modular Design

Mttr < 5mins

Accepts DC Input (DC/DC Converter)

Global Compliance (CE, Ul, NEBS)

Marine & Offshore Certifications

Patented Technology


Specifications


Model48-60/2000 HE
Part number241115.705
INPUT DATA
Voltage (nominal)185 - 275 VAC / 185 - 275 VDC
Voltage (operating range)85 - 300 VAC / 80 - 300 VDC
Current (maximum) @ nominal input, full load11.6 ARMS
Frequency45 - 66 Hz / 0 Hz
Power Factor> 0.99 at 50% load or more
THD< 5% at 100% load
ProtectionFuse in L & N, Varistor, Shutdown when input voltage is out of operating range
OUTPUT DATA
Voltage (default) 1)53.5 VDC (67 VDC in 60V mode)
Voltage (adjustable range) 1)39.9 - 72 VDC
Power (maximum) @ nominal input2000 W (@VOUT ≥ 48VDC)
Power @ 85 VAC750 W
Current (maximum) @ nominal input41.6 A (@VOUT < 48VDC)
Hold up time, 1500W output power>20ms; output voltage > 53.5 VDC (60V mode)
Current sharing (10 - 100% load)±5% of maximum current from 10 to 100% load
Static Voltage regulation (10 - 100% load)±0.5%
Dynamic Voltage regulation±5.0% for 10-80% or 80-10% load variation, regulation time < 50ms
Ripple & noise< 150 mVPP , 30 MHz bandwidth / < 2 mVRMS psophometric
ProtectionFuse , Short circuit proof, High temperature protection, Over voltage Shutdown
OTHER SPECIFICATIONS
Efficiency96.2 %
Isolation3.0 kVAC - input to output, 1.5 kVAC - input to earth, 500 VDC - output to earth
Low / high input voltage shutdown, High / low temperature shutdown, Rectifier
Alarms: Red LED

Failure, Overvoltage shutdown on output, Fan failure, Low output voltage

alarm, CAN bus failure

Rectifier in power de-rate mode, Remote output current limit activated, Input

Warnings: Yellow LEDvoltage out of range, flashing at overvoltage, Loss of CAN communication with controller
Normal operation: Green LED
MTBF (Telcordia SR-332 Iss.I method III (a))>350 000 (@ Tambient : 25 °C)
Operating temp. (5-95% RH n.cond. hum.)-40 to + 75°C [-40 to +167°F]
Max output power de-rates above temp / to45°C [113°F] / 1200W @ 75°C[167°F]
Storage temperature-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight109 x 41.5 x 327mm (4.25 x 1.69 x 13”) / 1.950 kg (4.3lbs)
DESIGN STANDARDS
Electrical safetyEN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, IEC 60950-1:2013 UL 60950-1:2011
EMC

EN 61000-6-1:2007, -6-2:2005, -6-3:2007 + A1:2011, -6-4:2007 + A1:2011,

IEC 61000-6-5: 2015, ETSI EN 300 386:2.1.1

MarineDNVGL-CG-03392)
Environment

ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3)

2011/65/EU (RoHS) & 2012/19/EU (WEEE)

Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other

operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised

OVS setting from controller select mode: OVS≤59.5V = 48V mode (42-58V), 59.5V<OVS<70.85 = 48V NiCad mode (39.9-66V) and OVS≥70.85V = 60V mode (52.5-72V). W hen de-energized module will return to 48V mode.

Only valid for part number 241115.705M


16kW Telecom system in outdoor cabinet

2U 8kW bulk feed power system

1U 8kW power shelf

China Eltek Flatpack2 Rectifier 48-60/2000 HE 5G Network Equipment Doc 241115.705.DS3 - V9 supplier

Eltek Flatpack2 Rectifier 48-60/2000 HE 5G Network Equipment Doc 241115.705.DS3 - V9

Inquiry Cart 0