

Add to Cart
Power Cable Busway Flammability Test Furnace
Uses
Suitable for the test of flame retardant, fireproof and fire
resistance of busbar trunking system (busbar trunking)
Technical parameters
1. Working voltage: AC380V±10% 50Hz; power consumption: 5KW
2. Furnace pressure measurement range: 0-100Pa measurement
accuracy:
3. Air flow: 0-50m3 / min measurement accuracy: ≤ ± 0.5 m3 / min
4. Combustion gas source: propane, liquefied gas
5. Gas tank capacity: 50kg × 4
6 Test temperature: programmed temperature 60min room temperature -
925 ° C 120min
7. Room temperature -1050 ° C 180min room temperature -1115 ° C
240min
8. Room temperature -1150 ° C
9. Furnace temperature: ± 15 ° C
10. The internal temperature of the test piece: ± 10 ° C
11. Test piece backfire temperature: ± 4 ° C
12. Temperature sensor:
13. In the furnace: 6 armored nickel-chromium-nickel-silicon
K-value thermocouples Accuracy class: II
14. Backfire: 6 armored nickel-chromium-nickel-silicon K-value
thermocouples Accuracy class: II
15. Timing range: 0-360min Timing accuracy: <±2s.
16. The maximum horizontal burning length of the sample: 2.4m
Vertical maximum burning length of sample: 1.6m
Equipment dimensions: length × width × height (3 × 2 × 2.5) m;
Standard
GA/T537-2005
How does fire retardant work?
Fire retardant contains salts (typically fertilizers) that alter
the way wildfires burn, decreasing fire intensity and slowing the
advance of the fire, even after the water in the fire retardant has
evaporated. The water in long-term fire retardants serves primarily
to aid in uniform dispersal of the chemical over the target area.