Home /Welding Equipment /

Electrical Oil Test Set Dielectric Dissipation Factor Volume Resistivity Tester

Electrical Oil Test Set Dielectric Dissipation Factor Volume Resistivity Tester

Brand Name:YUYANG
Certification:ISO
Model Number:DPT
Minimum Order Quantity:1 Set
Delivery Time:15 DAYS
Place of Origin:China
Contact Now

Add to Cart

Verified Supplier
Location: Dongguan Guangdong China
Address: B1505, FORTUNE PLAZA, No.1, Yuanmei Road, Nancheng District, Dongguan City, Guangdong Province, China
Supplier`s last login times: within 25 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

Insulation Oil Dielectric Dissipation Factor Volume Resistivity Tester


I. Introduction:


Automatic Dielectric Dissipation Factor Tester is a high-precision

instrument, which can be applied to measure dielectric loss angle and Volume Resistivity of
insulating oil etc.
This oil tan delta analyzer is integrated with oil cup for dielectric loss, temperature-control equipment,
temperature sensor, test-bridge for dielectric loss, AC trial electrical source, standard capacitor,
high resistance meter and DC high-voltage power etc.
The most advanced heating mode of high frequency induction is applied to the heating part of this iinsulation oil dissipation factor tester, which has the advantage of non-contact of oil cup and heating unit, homogeneous heating, quick velocity and convenient control etc. AC-DC-AC conversion mode is applied to AC trial electrical source so that the problem how to measure correctly under the fluctuation of voltage and frequency can be avoided. Even when the electric generator is working, the transformer oil volumn resistivity tester can operate correctly.
The inner standard capacitor is SF6 three-pole inflate capacitor, whose dielectric loss and
capacitance is not influenced by environmental temperature and dampness etc. In this way, the
accuracy of insulation oil dielectric loss tester is guaranteed conformably after a long-time application.

II. Specifications:

Condition of Use-5℃-40℃ RH<80%
Power SourceAC 220V±10% Without Frequency Limit
AC High Voltage Output400V-2200V ±2% Every 100V 50VA
DC High Voltage Output00V-2200V ±2%
Temperature Control Induction StoveMaximal Power 500W
Temperature Control Range<100℃
Temperature Measuring Error±0.5℃
Control Temperature Error0.1℃
Control Temperature TimeRoom Temperature 90℃ <20min

Measuring Range

tgδ Without Limit

Cx 15PF-300PF

Rx 10M-10T

Resolution

tgδ 0.001%

Cx 0.01pF

Rx 0.01

Precision

delta tgδ:±(Reading*0.5%+0.020%)

delta Cx :±(Reading*0.5%+0.5PF)

delta Rx :±Reading * 10%

Relative Dielectric Loss ConstantΕr Calculated Automatically
Volume Resistivityρ Calculated Automatically
Dimension450(L)×310(W)×360(H)
Net Weight21KG

China Electrical Oil Test Set Dielectric Dissipation Factor Volume Resistivity Tester supplier

Electrical Oil Test Set Dielectric Dissipation Factor Volume Resistivity Tester

Inquiry Cart 0