Fire Resistance Test Furnace IEC 60331 , Impact Test Equipment For Wire / Cable

Brand Name:YUYANG
Certification:IEC 60331, IEC 60331 Part 12, IEC 60331 Part 31
Model Number:YY613
Minimum Order Quantity:1 set
Delivery Time:8-10 work days
Payment Terms:T/T, L/C, Western Union
Contact Now

Add to Cart

Verified Supplier
Location: Dongguan Guangdong China
Address: B1505, FORTUNE PLAZA, No.1, Yuanmei Road, Nancheng District, Dongguan City, Guangdong Province, China
Supplier`s last login times: within 25 hours
Product Details Company Profile
Product Details

IEC 60331 Wire and Cable Fire-resistance Impact Testing Equipment


Descriptions:


Wire and Cable Fire-resistance Impact Tester is used to detect the fire resistance of cable wiring or power grid, burning in not less than 830 degrees, the flame, and exerts certain impact vibration, cable integrity test circuit.


Standards:


IEC 60331 Testing of wire and cable - circuit integrity under flame conditions

IEC 60331 Part 12 Instrument - at least under 830

IEC 60331 Part 31 Impact ignition procedures and requirements - rated voltages up to KV 0.6/1.0 cable


Main features:


1. The heat source for the belt type propane burner nozzle, its nominal length is 500mm, equipped with Venturi mixer;
2. 3 rows of combustion holes staggered arrangement, the front end of the burner average width: 15mm, hole diameter: 1.32mm, hole center distance: 3.2mm;
3. The test ladder frame of the installation cable is fixed on the support steel base;
4. In the process of testing according to the requirements of different vertical component cable size adjustment test on both sides of the ladder (ladder test length: 1200mm, height: 600mm, weight: 18 + 1kg);
5. The impact generator is a low carbon steel round bar with a diameter of 25 + 1mm and a length of 600 + 5mm;
6. Shock generator in parallel to the sample ladder frame pivot for the center free rotation, and the ladder frame top left 200 + 5mm;
7. The pivot rod will be layered in two parts, the longer part of the impact ladder frame, the length of 400 + 5mm;
8. The front burner combustion bottom distance not less than 200mm, and the distance from the wall of the box is not less than 300mm;
9. Burner axis from the lower end of the 40~60mm cable samples, from the longitudinal axis of the vertical axis about torch cable 100~120mm.