Add to Cart
CNG330 Series Low Frequency Online UPS 10-200KVA
Model:CNG330 10-200KVA(3Ph/3Ph)
Nominal Input Voltage: 380/400/415VAC
Output Power Factor:0.8
Model power | CNG330 10-200KVA | |||||||||||
10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | 120KVA | 160KVA | 200KVA | ||
Capacity | 8KW | 12 KW | 16 KW | 24 KW | 32 KW | 48 KW | 64 KW | 80 KW | 96KW | 128 KW | 160 KW | |
Input | ||||||||||||
Rated voltage | 400 Vac three-phase | |||||||||||
Voltage range | ±20% | |||||||||||
Frequency range | 45-65Hz | |||||||||||
Power factor | >0.92with harmonic filter | |||||||||||
Current harmonic distortion | <5%with harmonic filter | |||||||||||
Soft Start | 0-100% in10" | |||||||||||
Bypass Input | ||||||||||||
Rated voltage | 400Vac single-phase | |||||||||||
Permitted voltage range | ±15%(selectable from ±10% to ±25% from front panel) | |||||||||||
Rated frequency | 50/60Hz | |||||||||||
Permitted frequency range | ±2%(selectable from ±1% to ±5% from front panel) | |||||||||||
Standard features | Back Feed protection; split bypass line | |||||||||||
Batteries | ||||||||||||
Type | Maintenance-free lead-acid VRLA AGM / GEL;NICd | |||||||||||
Battery voltage | 384VDC | 480VDC | ||||||||||
Maximum recharge current(A) | 0.2×C10 | |||||||||||
AC ripple voltage | <1% | |||||||||||
Inverter Output | ||||||||||||
Number of phases | 3+N | |||||||||||
Rated voltage(V) | 400Vac | |||||||||||
Regulation of the output voltage | 380~424Vac phase/neutral(from control panel) | |||||||||||
Crest factor (Ipeak / Irms) | 3:1 | |||||||||||
Static stability | ±1% | |||||||||||
Dynamic stability | ±5% | |||||||||||
Frequency | 50/60Hz configurable | |||||||||||
Overload | 110% 125% 150% of the rated current for 5h/10'/1' | |||||||||||
Frequency stability | ±0.05% on mains failure;±2%(selectable from ±1% to ±5%)with mains supply present | |||||||||||
Remote signaling | Volt free contacts | |||||||||||
Remote controls | EPO and Bypass | |||||||||||
Communication | RS232 + romote contacts | |||||||||||
Operation temperature | 0ºC/ + 40ºC | |||||||||||
Relative humidity | <95% non condensing | |||||||||||
Noise | 54dBA at 1m | 50-65dBA at 1m | ||||||||||
Protection degree | IP20 | |||||||||||
Efficiency smart mode | up to 98% | |||||||||||
Compliance | Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive
2004/108/EC) |
Application:
Servers,
Local area Network(LAN),
Data centers,
Telecommunications,
Electro-medical equipment
High intelligence and reliable power supply:
Maximum battery care:
Easy to install:
Capability to install the UPS into any distribution system(neutral
not required on rectifier input);
Capability to separate the rectifier/bypass power networks and to
power these from two separate sources, without Galvanic isolation
(Necessary on UPS without an output transformer).
Back feed protection:
To avoid energy feeding back into the mains supply cause a fault
occur.
Maximum reliability and availability:
Connect up to 6 units in parallel or N+1 redundancy, even of
different power ratings.The UPS continue to work in parallel even
if one of the interconnecting communication cables is disconnected
(CLOOSED LOOP).
Low consumption level:
CNG330 can achieve efficiencies >98% thanks to selectable
Economy Mode which can be used in stable electrical environments to
provide power supply continuity when the mains fail.
Advance communication:
Compatible with TeleNetGuard for remote maintenance;
Advanced, multi-platform communication for all operation systems
and network environments: Watch & Save 3000 monitoring and
shut-down software included, with SNMP agent, for Windows 2008,
Vista,2003, XP; Mac OS X, Linux, Novell and most popular Unix
operating systems;
The UPS is supplied with a cable for direct connection to the
PC(Plug and Play);
RS232 double Serial port; Installation slot for an Emergency Power
Off (EPO) interface to allow the UPS to be switched off remotely in
an emergency;
Generator interface: enables desynchronisation of the UPS output
from a generator supply which may be subject to phase and frequency
variations. The interface also enables more economic use of the
battery charge.
Expandability:
The units can be connected in parallel up to 8 units to increase power availability or
redundancy. The single
module or the system can be expanded any time to suit power
requirements without influencing the initial investment.
Sales Service:
1. 2% spares together with shipment for urgent issue.
2. All of the necessary documents such as drawing, manaul etc.
3. We will provide the online service by mail
4. We also can desptach engineer to assist you solve the problem if
necessary. But you are requested to pay for the cost of ticket,
hotel etc.