Screened Single Core Medium Voltage Power Cables PVC Sheathed N2XSY

Brand Name:Chengtiantai
Certification:CE, ISO, IEC
Minimum Order Quantity:500 m
Delivery Time:7/15 working days
Payment Terms:L/C, T/T
Place of Origin:Shenzhen, China (mainland)
Contact Now

Add to Cart

Verified Supplier
Location: Shenzhen Guangdong China
Address: No.130 Jingsong 3rd road, Lisonglang Community, Gongming Street, Guangming District, Shenzhen, Guangdong, China, 518000
Supplier`s last login times: within 48 hours
Product Details Company Profile
Product Details

N2XSY Medium Voltage Power Cable single core 6/10 kV, 12/20 kV, 18/30 kV


XLPE Insulated, Copper conductor, singe core, screened, PVC sheathed


The singe core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 6/10 KV to 18/30KV and frequency 50Hz. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.


CONSTRUCTION:

1. CONDUCTOR

– Bare copper class 2 to IEC 60228, round, multiwire stranded and compact

2. CONDUCTOR SCREEN

– Inner semi-conducting coating

3. INSULATION

– Core insulation of cross-linked polyethylene (XLPE)

4. INSULATION SCREEN

– Outer conductive layer extruded and per-manently welded with the core insulation

Semi-conducting type
– Over the outer semi-conducting layer, a semiconducting tape must be used.

5. METAL SCREEN

– Annealed copper tapes with a minimum thickness of 0,1 mm.

Separator
– Over the screen as well as under outer sheath, a separating layer must be used (e. g. taping).

6. SHEATH

– Outer sheath of PVC compound

TECHNICAL DATA

Temperature range
– during installation up to -5°C

Operating temperature
– max. +90°C

Short circuit temperature
+250°C (short circuit duration max. 5 s)

Minimum bending radius
– 20 x cable Ø
Breaking strength: min. 200%
Tensile strength: min. 12,5 N/mm2

Nominal voltage
– U0/U 6/10 kV, 12/20 kV, 18/30 kV

Operating voltage, 50 Hz
– for 6/10 kV = max. 12 kV
– for 12/20 kV = max. 24 kV
– for 18/30 kV = max. 36 kV

Test voltage(V/5 min)
– for 6/10 kV = 21 kV
– for 12/20 kV = 42 kV
– for 18/30 kV = 63 kV


6/10 kV XLPE Insulated, Copper conductor, single core, screened, PVC sheathed


No.cores x
cross-sec.
Operation
voltage
max.
Nominal
voltage
U0/U
Insulation
thickness
Sheath
thickness
Nominal
value
Outer Ø
approx.
weight
approx.
Current ratings in air 30℃Current ratings buried 20℃maximum DC resistance at 20℃
mm²kVkVmmmmmmkg / kmAAΩ/km
1 x 35 rm126/ 103.41.620.66872051900.52
1 x 50 rm126/ 103.41.7228552452250.39
1 x 70 rm126/ 103.41.723.610863052750.27
1 x 95 rm126/ 103.41.825.513513703300.19
1 x 120 rm126/ 103.41.826.916224303750.15
1 x 150 rm126/ 103.41.928.619324904250.12
1 x 185 rm126/ 103.41.930.322995604800.1
1 x 240 rm126/ 103.42.032.728646655550.08
1 x 300 rm126/ 103.42.135.334597656300.06
1 x 400 rm126/ 103.42.238.645548907250.05
1 x 500 rm126/ 103.42.342.2557410308250.04
1 x 630 rm126/ 103.42.445.9686711909400.03

12/20 kV XLPE Insulated, Copper conductor, single core, screened, PVC sheathed


No.cores x
cross-sec.
Operation
voltage
max.
Nominal
voltage
U0/U
Insulation
thickness
Sheath
thickness
Nominal
value
Outer Ø
approx.
weight
approx.
Current ratings in air 30℃Current ratings buried 20℃maximum DC resistance at 20℃
mm²kVkVmmmmmmkg / kmAAΩ/km
1 x 35 rm2412/ 205.51.824.98602051900.52
1 x 50 rm2412/ 205.51.826.411382452250.39
1 x 70 rm2412/ 205.51.928.112813052750.27
1 x 95 rm2412/ 205.51.929.915703703300.19
1 x 120 rm2412/ 205.5231.318394303750.15
1 x 150 rm2412/ 205.5233.121744904250.12
1 x 185 rm2412/ 205.52.134.725405604800.1
1 x 240 rm2412/ 205.52.237.131206655550.08
1 x 300 rm2412/ 205.52.239.537467656300.06
1 x 400 rm2412/ 205.52.344.148638907250.05
1 x 500 rm2412/ 205.52.447.6590510308250.04
1 x 630 rm2412/ 205.52.551.3722011909400.03

18/30 kV XLPE Insulated, Copper conductor, single core, screened, PVC sheathed


No.cores x
cross-sec.
Operation
voltage
max.
Nominal
voltage
U0/U
Insulation
thickness
Sheath
thickness
Nominal
value
Outer Ø
approx.
weight
approx.
Current ratings in air 30℃Current ratings buried 20℃maximum DC resistance at 20℃
mm²kVkVmmmmmmkg / kmAAΩ/km
1 x 50 rm3618/ 308232.613632452250.39
1 x 70 rm3618/ 308234.316143052750.27
1 x 95 rm3618/ 3082.136.119193703300.19
1 x 120 rm3618/ 3082.137.522034303750.15
1 x 150 rm3618/ 3082.239.325564904250.12
1 x 185 rm3618/ 3082.240.929345604800.1
1 x 240 rm3618/ 3082.343.335406655550.08
1 x 300 rm3618/ 3082.445.741917656300.06
1 x 400 rm3618/ 3082.549.152468907250.05
1 x 500 rm3618/ 3082.654.6656110308250.04
1 x 630 rm3618/ 3082.758.4790611909400.03


*Dimensions and specifications may be changed without prior notice.


MEDIUM VOLTAGE CABLE TESTING


Routine tests:Sample tests:Type tests:
These non-destructive tests are normally carried out on all lengths manufactured.
- Conductor resistivity
- Spark test on oversheath
- Voltage tests on sheath
- D.C. voltage test on oversheath
These potentially destructive tests are normally carried out on every production run.
- Examination of conductor and dimensions
- Hot set test for XLPE insulation
- Insulation and oversheath thickness
- Four hour voltage test
These destructive tests are normally carried out in addition to the above tests on commencement of a particular cable supply to validate its design.
- Electrical type tests including bending and heat cycle
- Non-electrical type tests including mechanical properties after ageing and tests under fire conditions.

PACKING AND SHIPPING


Packing: steel wooden drum, other as required ; standard delivery length is 300 m



cable drum data


D1=Flange Diameter(mm)W=Useful Width (mm)D2=Barrel Diameter(mm)Approx empty
weight (kg)
number per 20 feet container
1250750600105 kg28

Our production in numbers


● Cable production started 1983
35 years of cable manufacturing experience

● Sales in 2016 about 500 million USD

100,000 m2 Production area
350 Will-trained employees
● Exported more than 22 countries
2 Manufacturing plant
1 R&D Center

200 Sets Of Testing Equipment

100 Testing Items
8 workshop
40 wire drawing machines
10 bunching machines
28 Extruder system
42 stranding machines
10 Braiding machines

Shenzhen chengtiantai cable operates certified management systems compliant with:
CertificatInformation
ISO 9001:2008
Quality management systems

Certificat ISO 9001:2008
- Shenzhen chengtiantai cable industry development Co.Ltd. ;
Certified through Guangdong quality Testing CTC Certification Co.Ltd.;
Valid until 13 January 2019
ISO 14001:2004
Environmental management systems

Certificat ISO 14001:2004

- Shenzhen chengtiantai cable industry development Co.Ltd. ;

Certified through Guangdong quality Testing CTC Certification Co.Ltd.;

Valid until 13 January 2019

OHSAS 18001:2007
Assessment specification for occupational health & safety management systemsenvironmental management systems
Certificat OHSAS 18001:2007
- Shenzhen chengtiantai cable industry development Co.Ltd. ;
Certified through Guangdong quality Testing CTC Certification Co.Ltd.;
Valid until 13 January 2019

Manufacturing Process Of Medium Voltage Power Cable

1. copper rod2. wire drawing3. wire stranding
4.Triple Extrusion Insulation5.Screening Process6. outer covering Process
7. Sheath Marking8. Packing9. Partial discharge Inspection

Some great shot on our manufacturing plant


Located in: Chengtiantai Industrial Park, Guangming New District, Shen zhen P. R. China 518106

Customer services:


RECOMMENDED ORDERING PARAMETERS

CONTACT

For prompt quotation / supplies please make sure your inquiries and your orders are
securing the following data :

1 - International or Special Standard. (Alternatively, the precise usage of the cable.)
2 - Rated voltage.
3 - Copper or Aluminium conductors.
4 - Size of each conductor.
5 - Insulation material : XLPE or others.
6 - Number and identification of conductors.
7 - Other requirements.
8 - Packing.
9 - Required delivery time.
10 - Required validity.

If this all seems a litle too technical for you, then why not get in touch with us.


We look forward to assisting you in identifying the best products for your specific application and to answer any questions you might have.


Tel:+86 755 6114 5028
Fax:+86 755 61137976
E-mail : cttcable@hotmail.com
Head office:chengtiantai Industrial Park, Lisonglang community, Gongming office, Guangming district, Shenzhen P.R. China 518106


WARRANTY


For a period commencing on the date shipped the Goods to Buyer and continuing for a period of 12 months thereafter.

China Screened Single Core Medium Voltage Power Cables PVC Sheathed N2XSY supplier

Screened Single Core Medium Voltage Power Cables PVC Sheathed N2XSY

Inquiry Cart 0