HV / LV Prefabricated Compact Transformer Substation Combined Substation ​


Service condition

  1. Altitude: ≤1000m (above sea level)
  2. Ambient temperature: Max. 40℃ Min. -25℃

Max. monthly average temperature: ≤ 35℃

Max. yearly average temperature: ≤ 25℃

  1. Relative humidity: Daily average value≤95%,monthly average value≤90%
  2. Max. daily difference in temperature: 25℃
  3. Sunlight intensity: 0.1W/CM2 (wind speed 0.5M/S);
  4. Outdoor wind speed : ≤35m/s;
  5. Pollution grade: Grade III ;
  6. Rain proof grade: Grade 3;
  7. The gradient on installation spot shall be not more than 3°;
  8. Ability of anti-earthquake: Horizontal acceleration of ground surface is 0.2g

Vertical acceleration of ground surface is 0.1g;

  1. Installation spot: The spot should has no fire,explosion danger,serious pollution,chemical corrosion and exquisite shake.

Customer should negotiate with manufacturer if the service condition is different from above.


Technical parameters


ItemsUnitParameters
High Voltage PartRated voltagekV12 24
Rated frequencyHz50
Rated current of main busbarA630
1mm power frequency withstand voltage (to earth and between phases/disconnecting fracture)kV42/48
Lightning impulse withstand voltage (to earth and between phases/disconnecting fracture)kV75/85
Rated short time withstand currentkA/s25/2
Rated peak withstand currentkA63
Rated short time making currentkA50
Rated transfer currentA1500
Breaking current of fusekA31.5 40
Low Voltage PartRated voltageV400
Rated current of main circuitA100-4000
Rated limiting short circuit breaking abilitykA80
Rated operating short circuit breaking abilitykA50 (65)
Rated short time withstand currentkA/1s50 (65)
Branch current,compensating capacityAccording to requirements of users
TransformerRated capacitykVA30-2000
Impedance voltage%4 4.5
Tapping range%±2×2.5 ±5
Connection symbolY, yn0 D, yn11
CaseProtection level of enclosureIP23
Sound leveldB≤50