XGN49 40.5kV SF6 Gas Insulated Metal-clad Switchgear for Indoor Power Distribution

Brand Name:Tianan Electric
Certification:IEC,IEEE,ISO
Model Number:XGN49
Minimum Order Quantity:1 set
Delivery Time:45 work days
Payment Terms:T/T, L/C, D/A, D/P, Western Union
Contact Now

Add to Cart

Verified Supplier
Location: Ningbo Zhejiang China
Address: 3/F, Building B7 , 999 Yangfan Road,High-tech Zone, Ningbo, China 315040
Supplier`s last login times: within 25 hours
Product Details Company Profile
Product Details

XGN49 SF6 Gas Insulated Switchgear Indoor Gas Insulation Metal-clad Switchgear


General Introduction:

XGN49-(12/24)40.5 series indoor gas-insulated metal-clad switchgear(hereinafter called "C-GIS panel") is a switchgear which uses a spring-operated vacuum circuit breaker,electrically operated three station isolation /grounding switch,transformer,lightning arrester as the main components,and completely seals all HV conductors in the metal-clad enclosure with SF6 gas as the insulating medium.

The product has features of flexible combinations,great safety,complete interlocking logic as well as extendibility,miniaturization and free for maintenance.So that it was commonly used in infrastructure construction for power station,power substation,movable transformer pack,rail traffic,buildings that have the 35kV or below nominal voltage.Especially for some sever environment like high altitude,heavy pollution and high humidity.

Installation and Test

The installation foundation construction of C-GIS switchgear shall comply with the relevant provisions in the DL/T5190 technical code for construction and acceptance of electric power construction,and shall be constructed according to the appearance and installation foundation dimensions of the switchgear.The installation foundation drawing and installation splicing diagram of the switchgear are shown below.(Note:If the secondary cables enter the panel from the top,it can be free from equipping the secondary cable hole and cable channel.


Parameters Table


ItemUnitParameter
Rated voltagekV40.5
Rated currentA5~2000
Rated frequencyHz50
Rated power frequency withstand voltage (1min)Phase to phase, Phase to earthkV95
Insulation Distance110
Rated Lightning impulse withstand voltagePhase to phase, Phase to earthkV185
Insulation Distance215
1min power frequency withstand voltage of Auxiliary control circuitV2000
Rated short-circuit breaking current (effective value)kA20 25 31.5
Rated short-circuit making current(peak time)kA50 63 80
Rated short time withstand currentkA20 25 31.5
Rated peak withstand currentkA50 63 80
Rated short-circuit keeping times4
Degrees of protectionIP67/IP4X
Every phase main return circuit resistanceμΩ≤250
Rated SF6 gas pressure (20°C)Mpa0.05
Min SF6 gas pressure (20°C)Mpa0.02
Annual SF6 gas loss rate%≤1
Rated voltage of auxiliary control circuitVDC110/220,AC220
Dimensions (Width×Depth×Height)mm

(600~1200) ×1400×2650