Home /Other Drive & Storage Devices /

11 kV Step Up Transformer Station Combined Substation For Wind Power

11 kV Step Up Transformer Station Combined Substation For Wind Power

Brand Name:TIANAN
Certification:ISO9001-2000, ISO9001, CCC
Model Number:ZGS-Z. F-/11
Minimum Order Quantity:1unit
Delivery Time:50 work days
Payment Terms:L/C, T/T, D/A, D/P
Contact Now

Add to Cart

Verified Supplier
Location: Ningbo Zhejiang China
Address: 3/F, Building B7 , 999 Yangfan Road,High-tech Zone, Ningbo, China 315040
Supplier`s last login times: within 25 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

11 kV Step Up Transformer Station Combined Substation For Wind Power

Product Description

Summarize
ZGS-Z.F-/11 series wind power combined transformer is a special power equipment integrating step-up transformer, HV current limited fuse, load switch, LV switch and related auxiliary equipments. It transforms the 0.69kV voltage produced by wind power motor into 35kV,and output the electricity through 35KV cable circuit, which is the ideal equipment in wind power complete set equipment.

Main technical parameter of transformer
Voltage combination
Rated voltage of HV side: 12kV
Rated voltage of LV side: 0.27kV, 0.3kV, 0.315kV, 0.4kV
HV tapping range+5% or + 2x2.5%
Connecting symbol: Dyn11 or Yyn0
Condensation controller and other auxiliary equipment can be added in the body as per clients' requests.
Insulation class: A class
No. of phases: three
Note: As per different requirement from client, the capacity of transformer can be customized.


Product technical parameter

11kV oil immersed load switch
Table 1


S/N
NameUnitParameter
1Rated voltageKV12
2Rated currentA315630
3Rated frequencyHz50
4Rated short-circuit withstand currentkA/2s12.520
5Rated peak withstand currentkA31.550
6Mechanical endurancetimes2000
71 min power withstand voltage (phase-to-phase, phase-to-earth)kV42
8Lightning impulse level (phase-to-phase, phase-to-earth)KV75

11kV Fuse
Table 2

Rated voltageFuse rated current ARated Max. breaking current kARemark
15.563, 80,100,125,15050off line

Lightning arrester
Table 3

Rated voltageContinuous operating voltageDC reference voltage (1mA)Nominal discharging currentNominal discharging current residual2ms square-wave current withstand value
17kV13.6kV≥24kV5kA(peak value)≤45kV (peak value)≥250A(peak value)