Product Details Company Profile
Product Details

0.02 Class High Precision Portable CT PT Analyzer with Printer


GF1061 portable CT PT analyzer is mainly used for field or lab testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt 7 inch touch TFT LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The CT PT Analyzer is the most complete and easy-to-use testing system for protection and metering CTs according to IEEE and IEC standards.

The CT Analyzer automatically determines all relevant current transformer values and compares the results with the selected standard. The device evaluates the current transformer as per the IEC or IEEE standard within seconds with the push of a button. it can test current transformer and potential transformer ratio error and phase rerror, Magnetization curve etc.
It facilitates fast and economical on-site testing and calibration of metering and protection current transformers. Manufacturers of current transformers, high voltage transformers and switchgear also use the CT Analyzer for tests during development and production.


MAIN FUNCTIONS

I. Current Transformer (CT)II. Voltage Transformer (PT)
1. Magnetization curve1. Excitation characteristic test
2. Transformation ratio test2. Transformation ratio test
3. Polarity3. Polarity
4. 5% and 10% error curve4. Ratio error, phase error
5. Accuracy limiting factor (ALF)5. Degauss
6. Degauss6. Calculation of knee point value
7. Ratio error, phase error7. Actual secondary load test (burden test)
8. Automatic calculation of excitation knee
point value
8. Resistance test
9. Actual secondary load test (burden test)
10. Resistance test 
11. Secondary time constant (Ts)
12. Remanence coefficient (Kr)
13. Transient dimensioning factor (Ktd)
14. Peak instantaneous error (Er)
15. Magnetizing inductance (LU)
16. Instruments security factor(FS)
17. Composite error

PARAMETERS


Electrical parameters
Accuracy0.05%
Power supplyAC 220V±10% or AC 120V±10%, 50/60Hz or Battery
Output voltage0-100Vrms
Output current0-5Arms (20A peak-value)
Output power0-400 VA (1500 VApeak)
Automatic frequency variation range0.1-60Hz
Equivalent excitation voltage≤5000V
Accuracy≤0.5%
Secondary winding DC resistance measurementRange0.1-1000Ω
Accuracy≤0.05%
Secondary actual load measurementRange5VA-1000VA
Accuracy≤0.5%±0.1VA
CT/PT phase error measurementAccuracy±1min (typical) / 3 min (guaranteed)
Resolution0.1min
CT ratio error measurementRange1-50000
Accuracy≤0.05%
PT ratio error measurementRange1-10000
Accuracy≤0.05%
Standards 
Reference standardsGB1207-2006, GB1208-2006, GB16847-1997
IEC60044-1, IEC60044-6, IEC61869-2, ANSI/IEEE C57.13
Safety standardsGB 4793.1-2007
EMCEMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2 /3 /4 /6
Mechanical parameters 
Overall dimension (L x W x H) (mm)280 x 250 x 160
Weight (kg)≤4
Environmental conditions 
Relative humidityRelative humidity 5%-95% not condensing
Operating temperature-10°C to +50°C
Storage temperature-20°C to +70°C
Altitude≤1000m