Add to Cart
Redundant Power Supply Module 24V 8A Redundante Schneider Electric Modicon Quantum 140CPS22400
Manufacturer: | Modicon Quantum |
Series: | Power Supplies |
Weight: | 2 lb |
Power supply type: | Redundant |
Input voltage: | 24 V DC 20...30 V |
Input current: | <= 3800 mA |
Inrush current: | 25 A 24 V |
14 A 20 V | |
Input power interruption: | 1 ms 20 V |
<= 100 ms | |
Associated fuse rating: | 5 A slow-blow |
Output voltage: | 5.1 V DC |
Power supply output current: | 8 A redundant |
Output overvoltage protection: | Internal |
Output overload protection: | 2.3 x maximum rated input voltage for 1.3 ms |
Power dissipation: | 6 + (1.8 x Iout) where Iout is in A |
Alarm output: | 1 NC 6 A 220 V power supply fault |
Local signalling: | 1 LED green power (PWR OK) |
Marking: | CE |
Module format: | Standard |
OTHER SUPERIOR PRODUCTS
Yasakawa Motor, Driver SG- | Mitsubishi Motor HC-,HA- |
Westinghouse Modules 1C-,5X- | Emerson VE-,KJ- |
Honeywell TC-,TK- | GE Modules IC - |
Fanuc motor A0- | Yokogawa transmitter EJA- |
standards | CSA C22.2 No 142 UL 508 | |
---|---|---|
product certifications | CUL FM Class 1 Division 2 | |
resistance to electrostatic discharge | 4 kV contact conforming to IEC 801-2 8 kV on air conforming to IEC 801-2 | |
resistance to electromagnetic fields | 10 V/m 80...2000 MHz conforming to IEC 801-3 | |
ambient air temperature for operation | 0...60 °C | |
ambient air temperature for storage | -40...85 °C | |
relative humidity | 95 % without condensation | |
operating altitude | <= 5000 m |
Sustainable offer status | Green Premium product | |
---|---|---|
RoHS (date code: YYWW) | Compliant - since 0901 - Schneider Electric declaration of
conformity Schneider Electric declaration of conformity | |
REACh | ||
Product environmental profile | Available End of life manual | |
Product end of life instructions | Available |
Warranty period | 18 months |
---|
Understanding and Using Cut Wire Detection
If the electrical current between the input and the sensor is more
than 1 mA, the wire is detected as not cut. If this current is less
than 1 mA, the wire is detected as broken and the corresponding
input’s red LED is lit.
If you install dry contact sensors, the corresponding input’s red
LED will be lit whenever the contact is open and the current will
be at 0 mA. To solve this and use cut wire detection properly,
Schneider Electric recommends installing a pull-up resistor on the
sensors so that the minimum current of 1 mA will be reached. You
can use a 15 kohms pull-up resistor or work out the value you need.
See the sensor
example in the illustration above.
Illustration
The following figure shows the wiring diagram for the 140CRP93100 module
power supply: 24 VDC
fuse: 1 A fast blow fuse
pull-up resistor (in sensor example): 15 kOhms
NOTE: There is only one group of 16 inputs. All common 24 V are
internally connected and all common 0 V are also internally
connected. The two pins of a same input (e. g: pin 1 and 2 for
input 1) are internally connected too so that you can use either
the right pin or the left one.