Redundant Power Supply Module GE Fanuc IC670ALG620 ANALOG IN RTD
Isolated Input Module
Description:
Current drawn from BIU power supply: 190 mA maximum
Digital Resolution: 15 bits plus sign
Operating temperature range: 0 to 55 Degrees C ambient
RTD types: 10, 25, 100, and 1000 ohm platinum; 10 and 100 ohm
copper; 100, 50, and 120 ohm nickel; 604 ohms and 1000 ohms
nickel/iron.
Resistance ranges: 0 to 500 ohms / 0 to 3000 ohms
Accuracy, at 25 C: RTD: +/-0.15% of reading, +/-0.3 to 0.5 degree
Celsius, depending on type
Temperature sensitivity (0 to 60C): +/-0.004% of reading, +/-1.5V
per C referred to input
Maximum lead resistance: 5 ohms per lead
Type of Device: RTD Input Module
Number of Channels: Four 3-wire and/or 4-wire RTDs
Scan time: 60 Hz: approximately 210 milliseconds per point, 50 Hz:
approximately 230 milliseconds per point.
Fault detection: Open RTD, input short, underrange, overrange, and
high/low alarm
Normal mode rejection: 60dB, at 50/60 Hz, 100% span
Common mode rejection: 120 dB at 50/60Hz, 100 ohm imbalance
Common mode voltage: 250 Vrms (350 VDC or peak AC)
Normal mode voltage: 100% overrange DC or peak AC operational 28
VDC or peak AC maximum
Isolation - User input to logic, user input to frame ground: 1500
VAC for 1 minute, 250 VAC continuous
Channel to Channel: 250 VAC continuous
IC670MDL233 120VAC 8 PT Isolated Input
IC670MDL240 120VAC Input 16 Pt. Grouped
IC670MDL241 240VAC Input 16 pt, 2 groups of 8
IC670MDL640 24VDC Pos./Neg. Logic Input 16 Pt. Grouped
IC670MDL641 48VDC Pos./Neg. Logic Input 16 Pt. Grouped
IC670MDL642 125VDC Pos./Neg. Logic Input 16 Pt. Grouped
IC670MDL643 5/12Vdc Pos./Neg. Logic Input 16pt Grouped
IC670MDL644 24VDC Pos./Neg. Logic Fast Input 16pt Grouped
IC670MDL330 12 - 120Vac 16 Point 1A Output
IC670MDL331 120VAC 2A Output 8 Pt. Isolated
IC670MDL730 24VDC 2.0A Output Pos. Logic, 8pt Electronic Short
Circuit Protection Module
IC670MDL740 12/24VDC 0.5A Pos. Logic Output 16 Pt. Grouped
IC670MDL742 5/12/24Vdc Neg. Logic Output, 16 point
IC670MDL930 Relay 2A 8 Pt. 6 Form A/2 Form C Isolated
IC670MFP100 Micro Field Processor
IC670CHS001 I/O Base, Barrier Style
IC670CHS002 I/O Base, Box Style
IC670CHS003 I/O Base, Connector Style
IC670CHS004 TC Cold Junction Compensation Base
IC670CHS101 I/O Base, Barrier Style, Hot Insertion
IC670CHS102 I/O Base, Box Style, Hot Insertion
IC670CHS103 I/O Base, Connector Style, Hot Insertion
IC670TBM001 Aux. Terminal Strip, Qty. 2 Barrier Style
IC670TBM002 Aux. Terminal Strip, Qty. 2 Box Style
The RTD Analog Input Module (IC670ALG620) accepts inputs from 4
independent 3-wireand/or 4-wire platinum, nickel, nickel/iron, or
copper RTDs.Module features include:
- Selectable resistance measurements in tenths of ohms, tenths of
degrees Fahrenheit, ortenths of degrees Celsius
- Individual channel configuration
- Selectable resistance ranges: 0 – 500 ohms and 0 – 3000 ohms
- Selectable RTD input as resistance or temperature (Celsius or
Fahrenheit)
- Reports high/low, underrange/overrange, open wire and input short
alarms.
- Uses optional discrete inputs and outputs for status and control.
- Two data acquisition rates based on 50 Hz and 60 Hz line
frequencies
- Configurable channel activation
Power Sources
No loop power is required for this module. The excitation current
for the RTDs is provided by the module, which automatically matches
the excitation current to each configured RTD type.
The RTD Input Module accepts four inputs from three-wire or
four-wire RTDs and converts the input level to a digital value.
Input spans support a variety of RTD types, as listed in the Module
Specifications section.
The analogital converter reads the voltage generated by each of the
four inputs. The A/D converter converts the differential
measurement into a binary value (15 bits plus sign), which is read
by the block’s microprocessor. The microprocessor sets the gain
required in the analogital converter for each individual input. The
gain is based on the RTD type that has been configured for that
input.
The microprocessor selects the input by means of a solid state,
optically-coupled multiplexer.Three measurements are made for each
input: Excitation current, RTD resistance including field wire
drop, and field wire drop. From these three measurements, the
module calculates the RTD resistance. A DC/DC converter circuit
isolates the field side from the logic circuits.
The following illustration shows connections for 3-wire and 4-wire
RTDs.
No loop power is required for this module. The excitation current
for the RTDs is provided by the module, which automatically matches
the excitation current to each configured RTD type.
I/O Terminal Block Terminal Assignments
The Terminal Block with box terminals (IC670CHS002) has 25
terminals for each module. Each
accommodates one AWG #14 (avg 2.1mm2 cross section) to AWG #22 (avg
0.36mm2 cross section) wire, or two wires up to AWG #18 (avg.
0.86mm2 cross section). When an external jumper is used, wire
capacity is reduced from AWG #14 (2.10mm2) to AWG #16 (1.32mm2).
The I/O Terminal Block with barrier terminals (IC670CHS001) has 18
terminals per module. Each terminal can accommodate one or two
wires up to AWG #14 (avg 2.1mm2 cross section).
The I/O Terminal Block with Connectors (IC670CHS003) has one 20-pin
male connector per module.
OTHER SUPERIOR PRODUCTS
Yasakawa Motor, Driver SG- | Mitsubishi Motor HC-,HA- |
Westinghouse Modules 1C-,5X- | Emerson VE-,KJ- |
Honeywell TC-,TK- | GE Modules IC - |
Fanuc motor A0- | Yokogawa transmitter EJA- |
Contact person: Anna
E-mail: wisdomlongkeji@163.com
Cellphone: +0086-13534205279