4 Cores 0.6/1kV CU PVC Insulated Power Cable Power Transmission Cable With IEC Certified

Brand Name:SHANCABLE
Certification:ISO,CE,IEC,TUV,KEMA
Model Number:CU/PVC/PVC
Minimum Order Quantity:Negotiable
Delivery Time:10 Days
Payment Terms:L/C, T/T
Contact Now

Add to Cart

Verified Supplier
Location: Shanghai Hunan China
Address: No.7577 Hunan Road, Pudong New District. Shanghai China
Supplier`s last login times: within 35 hours
Product Details Company Profile
Product Details

4 Cores 0.6/1kV CU PVC Insulated Cables IEC Certified good quality factory price PVC Cables


Construction

Conductor: Circular stranded copper conductor, conforms to IEC 60228 class 2

Insulation: PVC

Sheath: PVC type ST2 to IEC 60502, black

Note: Insulation color as per standards or customer requirement


Applications

Used for Power transmission and distribution line with voltage rated at 35kv and below.

For laying indoors and outdoors.Able to bear certain traction during installation, but not external mechanical forces.


Standards
International: IEC 60502, IEC 60228, (IEC 60332-3 for ZR-YJV only)
China: GB/ T 12706, (GB/T 18380-3 for ZR-YJV only)
Other standards such as BS, DIN and ICEA upon request

Technical data
Rated voltage: 0.6 / 1 kV
Maximum Conductor Temperature: under normal (90℃), emergency (130℃) or short circuit no more than 5 s (250℃) conditions.
Min. Ambient Temp. 0℃, after installation and only when cable is in a fixed position
Min. Bending Radius: 20 x cable O.D for single core
15 x cable O.D for multi core
Certificates
CE, RoHS, CCC, KEMA and more others at request


Electric Performance

1.Maximum Conductor DC resistance @ 20℃, Ω/km

Cross Section mm2CopperAluminum

Cross Section

mm2

CopperAluminum
250.7271.201850.09910.164
350.5420.8682400.07540.125
500.3870.6413000.06010.100
700.2680.4434000.04700.0778
950.1930.3205000.03660.0605
1200.1530.2536300.02380.0469
1500.1240.206

2. Single phase AC 50Hz voltage test or DC voltage test:

Rated voltage3.668.712182126
Single phase AC 50Hz test voltage12.52130.5426373.591

3. Partial Charge Test:

Test voltage is 1.73U0, the partial charge should not bigger than 10PC.




Voltage rating for XLPE Power CableNo. x Nominal Cross Section of Conductor No. x mm2
1 core2 core3 core3+1 core4core3+2 core4+1 core5 core
0.6/1 kV1x4 mm22x4 mm23x4 mm23x4 mm2 + 1x2.5mm24x4 mm23x4 mm2 + 2x2.5mm24x4 mm2 + 1x2.5mm25x2.5 mm2
1x6 mm22x6 mm23x6 mm23x6 mm2 + 1x4 mm24x6 mm23x6 mm2 + 2x4 mm24x6 mm2 + 1x4 mm25x4 mm2
1x10 mm22x10 mm23x10 mm23x10 mm2 + 1x6 mm24x10 mm23x10 mm2 + 2x6 mm24x10 mm2 + 1x6 mm25x6 mm2
1x16 mm22x16 mm23x16mm23x16 mm2 + 1x10 mm24x16 mm23x16 mm2 + 2x10 mm24x16 mm2 + 1x10 mm25x10 mm2
1x 25 mm22x 25 mm23x 25 mm23x25 mm2 + 1x16mm24x25 mm23x25 mm2 + 2x16mm24x25 mm2 + 1x16mm25x16 mm2
1x35 mm22x35 mm23x 35 mm23x35 mm2 + 1x16mm24x35 mm23x35 mm2 + 2x16mm24x35 mm2 + 1x16mm25x25 mm2
1x50 mm22x50 mm23x 50 mm23x50 mm2 + 1x25mm24x50 mm23x50 mm2 + 2x25mm24x50 mm2 + 1x25mm25x35 mm2
1x70 mm22x70 mm23x 70 mm23x70 mm2 + 1x35mm24x70 mm23x70 mm2 + 2x35mm24x70 mm2 + 1x35mm25x50 mm2
1x95 mm22x95 mm23x 95 mm23x95 mm2 + 1x50mm24x95 mm23x95 mm2 + 2x50mm24x95 mm2 + 1x50mm25x70 mm2
1x120 mm22x120 mm23x 120 mm23x120mm2 + 1x70mm24x120 mm23x120mm2 + 2x70mm24x120mm2 + 1x70mm25x95 mm2
1x150 mm22x150 mm23x 150 mm23x150mm2 + 1x70mm24x150 mm23x150mm2 + 2x70mm24x150mm2 + 1x70mm2
1x185 mm22x185 mm23x 185 mm23x185mm2 + 1x95mm24x185 mm23x185mm2 + 2x95mm24x185mm2 + 1x95mm2
1x240 mm23x 240 mm23x240mm2 + 1x120mm24x240 mm23x240mm2 + 2x120mm24x240mm2 + 1x120mm2
1x300 mm23x 300 mm23x300mm2 + 1x150mm24x300 mm23x300mm2 + 2x150mm24x300mm2 + 1x150mm2
1x400 mm2