BS5467 Cu/XLPE/PVC/AWA/PVC 0.6/1kV XLPE Insulated Power Cable for Fixed Installation

Brand Name:SHANCABLE
Certification:ISO,CE,IEC,TUV,KEMA
Model Number:YJV
Minimum Order Quantity:Negotiable
Delivery Time:10 Days
Payment Terms:L/C, T/T
Contact Now

Add to Cart

Verified Supplier
Location: Shanghai Hunan China
Address: No.7577 Hunan Road, Pudong New District. Shanghai China
Supplier`s last login times: within 35 hours
Product Details Company Profile
Product Details

BS5467 Cu/XLPE/PVC/AWA/PVC 0.6/1kV Used for Fixed Installation


Cable Application


Cu/XLPE/PVC/AWA/PVC power cable may be used for fixed installation indoors and outdoors in cable ducts or directly in the ground.

Technical Information

Conductor Material:Copper, IEC60228
Conductor Shape:50mm² up to 400mm² Circular
Conductor Flexibility:Stranded class 2
Outer Sheath:PVC, IEC60502
Inner Sheath:PVC, IEC60502
Insulation:XLPE (Cross-linked Polyethylene), IEC60502
Armour Type:Aluminium wires
Colour:Black
Lead Free:Yes
Rated Voltage Uo/U (Um):600/1000V, BS5467
Installation Temperature:Minimum: 0°C Maximum: 60°C
Installation Type:Outdoor Direct burial
Operating Temperature:Minimum: -15°C Maximum: 90°C
Short-circuit Maximum Conductor Temperature:250°C
Flame Retardant:IEC 60332-1 and BS EN 50265-2-1
Bending Radius:50mm² up to 1000mm² = 6 x Ø

Rated voltage:0.6/1kV Low Voltage
Maximum Conductor Temperature: under normal (90℃), emergency (130℃) or short circuit no more than 5 s (250℃) conditions.
Min. Ambient Temp. 0 OC, after installation and only when cable is in a fixed position
Min. Bending Radius: 20 x cable O.D for single core without armor
15 x cable O.D for multi core without armor
15 x cable O.D for single core with armor
12 x cable O.D for multi core with armor

Standards: International: IEC 60502, IEC 60228, (IEC 60332-3 for FR-type only)
China: GB/T 12706, (GB/T 18380-3 for FR-type only)
Other standards such as BS, DIN, VDE and ICEA upon request

Installation

1. The installation temperature should not over 20℃, If the ambient temperature is lower than 0℃, the cable should be preheated.
2. The bending radius of cable should not less than 8 times.
3. After installation, the cable should with stand voltage test for 15min. 3.5kv D.C.


China BS5467 Cu/XLPE/PVC/AWA/PVC 0.6/1kV XLPE Insulated Power Cable for Fixed Installation supplier

BS5467 Cu/XLPE/PVC/AWA/PVC 0.6/1kV XLPE Insulated Power Cable for Fixed Installation