2W 3-hour LiFePO4 battery Emergency LED driver with Battery Auto Testing and Self-testing Optional with 5 Years Warranty

Brand Name:Merrytek
Certification:CE, UKCA, UN38.3, MSDS
Model Number:KE027-02AM180HE
Minimum Order Quantity:100
Delivery Time:1, Sample and small order: Within 5 working days after receiving your payment. 2, Bulk order: 3-4 weeks after receiving deposit.
Payment Terms:T/T or Western Union
Contact Now

Add to Cart

Verified Supplier
Location: Shenzhen Guangdong China
Address: 101-1101, Building 17, Dianda Guyuan Industrial Park, Mashantou Community, Matan Street, Guangming District, Shenzhen
Supplier`s last login times: within 33 hours
Product Details Company Profile
Product Details

2W 3-hour LiFePO4 battery Emergency LED driver with Battery Auto Testing and Self-testing Optional with 5 Years Warranty



1. Description


1) Constant power output LED emergency power supply with a wide output voltage range.
2) Input relay switching.
3) High safety, high performance, long life LifePO4 battery.
4) With battery management.

5) Manual test and automatic test selection.



2. Parameters

Charge Part

KE027

02AM180HE

03AM180HE

04AM180HE

05AM180HE

Rated input voltage

220-240Vac 50Hz/60Hz

Rated input current

0.06A Max. @230Vac

Input inrush current

10A(Twidth=100us 50% Ipeak )@230Vac(Cold start at full load )

Power factor

≥0.5@230Vac

Input power

<4W@230Vac

Battery charging current

250mA

250mA

350mA

350mA

Battery charging time

24 hours Max.

Emergency Part

Operating mode

Emergency mode

Load type

LED

Emergency power

2W

2.5W

4W

5W

Emergency time

3hours

Load output current

25-10mA

31-12mA

50-20mA

65-25mA

Load output voltage

80-200Vdc

Battery

LifePO4 (The battery capacity meets the emergency time at 25)

6.4V 1.8Ah

6.4V 1.8Ah

6.4V 3.6Ah

6.4V 3.6Ah

Battery warranty

Warranty 5 years @5~60.

Exception Driver Requirements

Surge current

8A

Input current

3A Max.

Output current

2A Max.

LED Indication
(Manual test)

Charging

Green light

Fault

Green light off

Emergency Function Test

Manual test

Default

Auto test

Settable

Auto Testing

Fault/test / Status

Reason

Charge Indicator Status

The battery is fully charged and operational

Standard daily use


solid green

Battery Charging

Initial Charge/Battery Top Up



Flashing green 1 sec on 1 sec off

Auto Test 3 Hours (every 12 months)

Periodic self-test



Flashing Green 3 sec on 1 sec off

Auto Test 5 Min (every 30 days)

Periodic self-test



Flashing Green 3 sec on 3 sec off

Duration test fault

Automatic test failed



Flashing Red 0.5 sec on 0.5 sec off

LED fault

Not plugged in or damaged/faulty






Flashing Red 2 sec on – 2 sec off

Battery Disconnected/Faulty

Not plugged in or damaged/faulty


solid red

Emergency protection

Battery over-charge/deep discharge protection

Yes

Output over-voltage protection

Yes

Output overload protection

Yes

Output short circuit protection

Yes

Operating

Environment

Operating temperature/humidity

0…+50℃,humidity:20%-75%(without condensation)

Storage temperature/humidity

-5-35

Case Max. Temp(Tc)

75

Safety

& EMC

Withstand voltage

3000Vac 5mA 60s (Input “L N” – output “SEC+ SEC-)

Safety standard

EN61347-1, 60598-2-22, 61347-2-7, 62034

EMC standard

EN55015, EN61000-3-2, EN61000-3-3

Battery standard

UN38.3

Environmental protection requirements

Compliant with RoHS

Certification

CE

Others

Input/output(terminal/wiring) specification

Press terminal, wire diameter: 0.5- 0.75 mm2

IP rating

IP20

Type of protection

Class 2

Installation type

Built-in installation

Installation dimension

146*30*22.5mm

Packaging requirement

White box+Instruction manual+clapboard+outer carton(K=A)

Weight

75g (driver)

Lifespan

5 Year @Ta

Notes:

All parameters are tested on the input voltage 230VAC, environment temperature 25, unless otherwise specified.

3. Dimension (Unit:mm)

2W 3-hour LiFePO4 battery Emergency LED driver with Battery Auto Testing and Self-testing Optional with 5 Years Warranty

2W 3-hour LiFePO4 battery Emergency LED driver with Battery Auto Testing and Self-testing Optional with 5 Years Warranty

2W 3-hour LiFePO4 battery Emergency LED driver with Battery Auto Testing and Self-testing Optional with 5 Years Warranty

2W 3-hour LiFePO4 battery Emergency LED driver with Battery Auto Testing and Self-testing Optional with 5 Years Warranty



4. Wiring Diagram


2W 3-hour LiFePO4 battery Emergency LED driver with Battery Auto Testing and Self-testing Optional with 5 Years Warranty

OR

2W 3-hour LiFePO4 battery Emergency LED driver with Battery Auto Testing and Self-testing Optional with 5 Years Warranty

5. Manual Test and Autotest switch

2W 3-hour LiFePO4 battery Emergency LED driver with Battery Auto Testing and Self-testing Optional with 5 Years Warranty

6. Wire Preparation

2W 3-hour LiFePO4 battery Emergency LED driver with Battery Auto Testing and Self-testing Optional with 5 Years Warranty

  • Solid or Stranded wire type: 0.5 -0.75 mm2
  • To access or remove the wires from the terminals, use a screwdriver to push the buttons down


7. Manual Test & Operation Instructions

1) Before installation, set Pin short: Manual Test.

2) Connect the wire according to the wiring diagram.

3) L, N power on, Switch on S1. Then the load lamp turns on, the emergency driver indicator light will turn green, emergency power supply will be normally charging. Turn off Switch S1, and the load lamp turns off.

4) Emergency Simulation: Switch on, the load lamp turns on, press the switch(TEST SWITCH), then switch to emergency mode, the indicator light of the emergency driver will be extinguished. Release the switch(TEST SWITCH), then the lamp is powered by the LED driver, the indicator light will turn on.


8. Automatic Test & Operation Instructions

1) Before installation, set the pin open for the automatic test.

2) Connect the wire according to the wiring diagram.

3) L, N power on, start the clock, and periodic self-test. To replace the battery, turn off the power supply, Re-time.


9. Battery Application Notice

1) The battery should be recharged and discharged semiannually in normal use conditions.

2) Do not connect to the circuit when the battery is not used to prevent over-discharging of the battery due to self-consumption of the circuit board.

3) Please keep the battery away from the heat source when installing and using it, and only be allowed to use it in a certain working temperature range.

4) The battery should be stored in a cool and dry environment.

5) After a long time of storage, the battery is cycled every 12 months as required.

6) AC power is off, and the clock lasts for 7 days. Power on and re-time. To replace the battery, turn off the power supply, Re-time.






China 2W 3-hour LiFePO4 battery Emergency LED driver with Battery Auto Testing and Self-testing Optional with 5 Years Warranty supplier

2W 3-hour LiFePO4 battery Emergency LED driver with Battery Auto Testing and Self-testing Optional with 5 Years Warranty

Inquiry Cart 0