12KV 10KA Safety Substation Lightning Arrester , Metal Oxide Surge Protector without Gaps

Brand Name:YONGDE
Certification:ISO9001/KEMA
Model Number:YH10W5-12
Minimum Order Quantity:1pcs
Delivery Time:21days per container
Payment Terms:T/T or western Union or L/C or PayPal
Contact Now

Add to Cart

Verified Supplier
Location: Hangzhou Zhejiang China
Address: Yinghu Economy Developing Zone, Fuyang Hangzhou City, Zhejiang Province, China
Supplier`s last login times: within 42 hours
Product Details Company Profile
Product Details

YH10W5-12 Substation Surge Arrester without Gaps, KEMA


Description:


YongDe Surge Arresters can be applied to a variety of systems including substation equipment, AC-DC converters, railway power system and power distribution units ranging from 0.25kV to 765kV systems. These surge arresters demonstrate excellent protection properties. YongDe surge arresters incorporate YNR elements (YongDe Non-linear Resistor ZnO Elements) with superior non-linear voltage-current characteristics, high quality and reliability. Metal oxide type surge arresters offer such special features inherent in the gap-less structure, such as a quick response to surge voltage, high energy dissipation capability, safe operation, compactness / lightweight and freedom from pollution.


Product characteristic:

1. Small size,Light weight,resistance to impact,no collision damage during

transportation,flexible installation,suitable for use in the switch cabin.
2. Special structure,the overall compression molding,no air gap,good sealing

performance,moisture-proof and explosion-proof
3. Large creepage distance,good hydrophobicity,strong stain resistance,stable

performance and reduce operation maintenance.
4. Unique formula of zinc oxide varistor, small leakage current,slow aging,long

service life.
5. With DC reference voltage,rectangular flow capacity and high current and large

current withstand capacity are higher than standard requirement.


Specifications:


TypeYH10W5-12
Rated voltage---------kV124/10µS High current impulse kA100
MOCV ----------------kV10.2Lightning impulse withstand kV110
Nominal Current-------kA10Power frequency voltage withstand(dry/wet)kV28
Residual voltage of steep impulse----at 5kA(kV)360.1S TOV--------------kV14.4
8/20µS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV)331S TOV----------------kV13.8
Residual voltage of switching impulse current kV (peak value)----at 1kA (kV)31.510S TOV---------------kV13.2
1mA D.C reference voltage (kV)171200S TOV-------------kV12
Line discharge level1Creepage distance ----mm434
2mS long duration impulse current A400Material employed in series non-linear resistorZinc Oxide

Packing details:


1) Size: 430mmX145mmX160mm with 3pieces per carton
2) Packing: Carton with polyfoam insert parts
3) Weight: 4.2kg/carton
4) Loading Port: Ningbo/ Shanghai(Or as customer requirement)
5) Loading Ability: 20'GP 4500sets / 40'GP 9000sets


Working condition:


1) Environment temperature: -40--+40 degree
2) altitude: <1000m
3) 48HZ

4) Power frequency voltage should not be more than continuous running voltag
5) Max wind speed should be less than 35m/s
6) Earthquake intensity should be less than 7 degree
7) If used in contamination area, should be noted in advance.

China 12KV 10KA Safety Substation Lightning Arrester , Metal Oxide Surge Protector without Gaps supplier

12KV 10KA Safety Substation Lightning Arrester , Metal Oxide Surge Protector without Gaps

Inquiry Cart 0