48V 300A DC battery load bank

Brand Name:Triumph Load
Certification:ISO9001:2008
Model Number:48V 300A DC battery load bank
Minimum Order Quantity:1 set
Delivery Time:within 35 days
Payment Terms:T/T,L/C,Western Union
Contact Now

Add to Cart

Active Member
Location: Shijiazhuang Hebei
Business type: Manufacturer, Exporter
Address: No68 Jianshe Street,Shijiazhuang,Hebei,China
Supplier`s last login times: within 47 hours
Product Details Company Profile
Product Details

Introduction

48V 200A battery test dummy load bank (namely battery discharger, battery load bank, battery discharge tester), is designed for the capacity test and maintenance of continuous battery sets through intensive discharging. The unit features in its LED display, timing function and automatic low voltage protection; Automatic constant current control for battery capacity tests.

Main features

1). Display: LED display all parameters and test data in real-time with English menu. Display testing data: voltage, current, capacity, discharging time, etc.

2). Control pattern: keyboard set the whole battery set protective voltage, current, capacity, discharging time.

3). Automatic stop: It can stop testing automatically meet following conditions: test time out, testing capacity out and protective voltage out.

4). Protection: Perfect automatic protection and alarm function: When high temperature, opposing connection, automatic protection power–off and sending alarm sound.

5). Power-consuming is special alloy resistor with small temperature drift, patent technology design, high power density, and safe.

6). Portable, with small volume, forced air cooling.

Technical specification

Model

DC48-300

Battery Rated Voltage

DC 48V

Discharging Voltage

Discharge 12-60V: 48V±10% guarantee the highest current 300A, can discharge for long time, changing according to Ohm's Law.

Protective Voltage

1-60V

Discharging Current

1-300A

Discharging Time

1 minute-99 hours and 59 minutes

Discharging Capacity

1-9999Ah

Group Voltage Tolerance

±1%

Current Tolerance

±1%

Constant-current Discharge Control

±(0.3%+0.2A)

Power Supply

Single phase voltage 220VAC,50Hz

Cooling

Forced air cooling

Environment temperature

-10℃ - +40℃

Volume(mm)

440*330*575mm(width*depth*height)

Weight(kg)

30kg

China 48V 300A DC battery load bank supplier

48V 300A DC battery load bank

Inquiry Cart 0